Honeywell EN2Z-0906GE51 R0708 Benutzerhandbuch

Seite von 160
USER GUIDE 
 ARENA/ RANGER
 
 
 59 
 
EN2Z-0906GE51 
R0708 
 
Cross Reference of iLON 10 Settings and ARENA Settings 
ARENA configures the iLON 10 when creating the site (see in “Create Site” section). 
If the iLON 10 configuration, e.g. user name or password, was changed manually 
afterwards, the ARENA settings must be changed accordingly. If ARENA settings 
and the iLON 10 settings are out of sync it may happen that the iLON 10 cannot be 
contacted anymore. For the accommodation of settings, use the following table.  
 
General Settings page of iLON 10 
iLON 10 Setting 
ARENA Setting 
Comment 
IP Address 
Outgoing connection: Remote Site IP 
Address 
Used in LAN scenarios to contact the iLON 
10. User needs Administrator privilege 
Subnet Mask 
Outgoing connection: Subnet Mask 
Used in LAN scenarios to define the subnet 
to which the iLON 10 is connected. 
User needs Administrator privilege 
Gateway Address 
Outgoing connection: Gateway 
Address 
Used in LAN scenarios to resolve 
addressing if the iLON 10 and the 
supervisor PC are in different subnets. 
Contact the I.T. administrator to get the 
gateway’s IP address. 
Explicit message -> Message with 
Code From / To 
Used to send an alarm from the controller 
to the iLON 10. This has to be set "from 76 
to 76" and the setting has to be enabled. 
Otherwise no alarms will be sent out via 
the iLON 10. 
PPP Settings page of iLON 10 
iLON 10 Setting 
ARENA Setting 
Comment 
Serial Port Baud Rate 
Should be set to 57600 
Local IP Address for incoming calls 
IP Address for PPP connections via 
modem. This is automatically generated 
by the ARENA site administration for 
Dial-Up scenarios.  
Use Static IP Address-> IP Address 
IP Address for PPP connections via 
modem. This is automatically generated 
by ARENA site administration for Dial-Up 
scenarios.  
Profile 1 -> User Name 
Incoming Connection->User Name 
User Name which the supervisor PC 
uses to authenticate an incoming call 
from the iLON 10. 
Profile 1 -> Password 
Incoming Connection->Password 
Password which the supervisor PC uses 
to authenticate an incoming call from the 
iLON 10. 
Profile 1-> Phone Number 
Incoming Connection -> Local Phone 
Number 
Phone number under which the 
supervisor PC can be reached for Dial-
Up scenarios. 
Profile 1 -> Disconnect if idle for 
This time out applies if no LON 
connection can be made to the alarm 
receiver (ARENA). This should never 
happen. A good default would be 120 
sec. 
Profile 1 -> Modem Init String 
Incoming Connection -> Advanced 
settings -> Initialization string 
Init string which the iLON 10 uses each 
time it triggers a dial-out via modem. Via 
the init strings, special modem 
configurations can be made. Typical 
examples are: 
X0: Do not wait for dial tone 
M0 instead M1 to switch off the modem 
speaker. 
A good default string for many modems 
is E0Q0V1S0=0&C1M1 
If you need special settings, consult your 
modem manual and a description of the