10
CHECKOUT
Error Messages
There are seven error messages that can display in response 
to T775 software or hardware problems. The error Codes that 
can flash on the display are:
• SF: Sensor Failure
— A flashing SF indicates an out-of-range or defective 
sensor. Make sure that the sensors are connected 
properly. For T775A,C all loads de-energize when this 
error message flashes.
— For the T775B,D the loads controlled by the out-of-
range sensor de-energize. The display flashes SF to 
indicate which sensor is defective or in error. In the 
event that only one sensor is defective, the remaining 
sensor and its load(s) operate normally. Only the 
load(s) controlled by the defective, out-of-range, or 
unconnected sensor de-energize. 
NOTE: Sensor values below -40°F or above 220°F are 
out-of-range.
• EF: EEPROM Failure
— The values read back from the EEPROM are not the 
same as written into the EEPROM. This error cannot 
be field repaired. Replace the device. The EEPROM is 
not intended to be field repaired.
• CF: Calibration Failure
— A calibration resistor reading was not within the range 
of the Analog to Digital converter. This error cannot be 
field repaired. Replace the device.
• OF: Stray Interrupt Failure
— An unused interrupt occurred. This error cannot be field 
repaired. Replace the device.
• CE: Configuration Error
— The device hardware was configured to a nonexistent 
device. This error cannot be field repaired. Replace the 
device.
• OE: ROM Error
— The internal Read Only Memory (ROM) of the micro-
processor is defective. This error cannot be field 
repaired. Replace the device.
• AE: RAM error
— The internal Random Access Memory (RAM) of the 
microprocessor is defective. This error cannot be field 
repaired. Replace the device.
Setpoint Calibration
To maintain temperature accuracy, use 18 AWG two-conductor 
sensor wires. If the length of the sensor wire exceeds 400 feet, 
recalibration will be necessary to maintain accuracy. Table 4 
shows the corresponding temperature offset to use for different 
sensor wire lengths. This temperature offset should be added 
to the desired temperature setpoint for these applications. 
Refer to programming instructions in the Programming section 
for entering temperature setpoints.
Table 4. Temperature Offset Based on Wire Length.
After the controller is installed and wired, apply power. Make 
initial adjustments and desired settings:
1. As shown in Fig. 10, record the sensed temperatures for 
both Sensor A and Sensor B as displayed on the device. 
Use the Select key to advance through the programming 
loop to determine and then write, on the Checkout Table 
(Fig. 10), the loads controlled by each sensor.
2. Write the operating mode (heat or cool) for each stage in 
the Checkout Table (Fig. 10).
3. Write the sensed temperature for each load on the 
Sensed Temp line.
4. Write the differential for each load on the Differential line. 
5. Write the setpoint for each stage (Off temperature). Cal-
culate the “On Temperature” for each stage.
NOTE: “On temperature” is setpoint plus differential for 
cooling, and it is setpoint minus differential for 
heating.
6. Plot the on and off (open/closed) values at which the 
device will energize and de-energize each output load, 
(Refer to the Device Programming Worksheet.) 
7. Verify which loads are energized by using the Checkout 
Table (Fig. 10). As shown in the example, the display 
indicates, in the lower right corner, energized stages. If 
no stages are energized, the words “stage energized” 
will not appear.
NOTE: If the sensed temperature is between the On 
and Off temperatures, the load may either be 
energized or de-energized. Refer to the Control 
Algorithm section (in Operation) for further 
explanation.
8. If an error message flashes, refer to the description of 
these messages. If SF flashes:
a. Check sensor connections.
b. If properly connected and SF continues to flash, 
check the sensor location to make sure it is located 
in an ambient condition that is within the sensor 
capability (-40° to +220°F).
9. If an error message other than SF flashes, the device 
cannot be field repaired. Replace the device.
Sensor Wire Length
Calibration Offset
0 to 399 ft
None required.
400 to 599 ft
1.0 degrees
600 to 799 ft
2.0 degrees
800 to 1000 ft
3.0 degrees