Honeywell T775A Benutzerhandbuch

Seite von 16
T775A,B,C,D REMOTE TEMPERATURE CONTROLLER
63-2489—2
8
2. For two sensor models (T775B), determine which loads 
will be controlled from sensor A or sensor B and enter on 
the worksheet.
3. Determine setpoint (Setpt) and switching differential 
(Diff) for each load and enter on the worksheet.
4. Refer to the Control Algorithm subsection of Operation 
section to calculate the load on and off temperatures. 
Enter them on the worksheet.
NOTE: Remember that the on/off outputs are off at 
setpoint in both heating and cooling operating 
modes. When in cooling mode, the load turns 
off at setpoint plus the differential. When in 
heating mode, the load turns on at setpoint 
minus the differential.
CAUTION
The T775 will not allow the user to program for both 
heating and cooling loads to be energized at the 
same time.
If this situation results, cooling loads will be energized 
and heating loads will be prevented from energizing. 
The number (1,2,3,4) of these nonenergized loads will 
flash along with the word HEAT to indicate a call for 
both heating and cooling loads controlled by one 
sensor has occurred and to alert the user to reprogram 
the affected control values.
5. Remove the T775 cover and enter the values listed on 
the worksheet and the date in the first column on the 
label inside the T775 cover.
Keypad Programming and Display
The T775 utilizes a Liquid Crystal Display (LCD) for interactive 
prompting during programming and display of sensed and 
assigned setpoint and differential values. User programming of 
the T775 is accomplished through the four programming keys.
Programming Keys
The four programming keys are Select, Up and Down (arrows), 
and Enter:
• Select: Sequentially prompts the user about what parameter 
is being displayed. After the last parameter value is viewed, 
pressing the Select key again displays the control values 
from the beginning of the display loop. The parameters are:
— setpoint, 
— differential, 
— stage energized, 
— heat or cool (operation mode), 
— 1,2,3,4 (indicating assigned stage).
• Up and Down: Allow the displayed parameter to be 
increased or decreased. After pressing Select, a control 
value can be changed using these keys. Control values 
increase or decrease by 1°F or 1°C each time an arrow key 
is pressed.
• Enter: Places the new value in the microprocessor memory.
IMPORTANT
Control values/operations are not placed in the micro-
processor memory until the Enter key is pressed.
Press the Select and Enter keys at the same time to change 
the control algorithm from heating to cooling or from cooling to 
heating:
— Heating and cooling parameters are not displayed during 
normal Select key sequences.
— The only parameters displayed after pressing the Select 
and Enter keys at the same time are the stage indication, 
and the word heat or cool.
— To change the operation from heating to cooling (or vice 
versa) for a desired output stage, use the arrow keys.
— The next stage of heat or cool assignment appears after 
pressing the Select key. When all stages are programmed, 
the display reverts to sensed temperature and load 
energized status.
NOTE: Control values and operation selection remain in the 
device memory even after the power is removed.
Display
Once power is applied or restored to the device, the display 
counts down from 210 until the display reads zero. During this 
time all previously energized outputs de-energize. This is 
intended to protect compressors in the event of a power failure.
NOTE: To avoid viewing the entire countdown, press the 
Select key.
The LCD display now shows what it normally reads:
— load (sensed) temperature, 
— stages energized,
— and, for two sensor devices, the sensor (Sensor A or 
Sensor B) being read.
NOTE: At any time during programming, a 60 second pause 
between key presses reverts the display to indicate 
the sensed temperature and stage status.
For two sensor applications, the user has three options for 
display of sensed temperature. The display can be configured 
to:
— lock onto continuous Sensor A,
— lock onto continuous Sensor B sensed temperature,
— alternate between Sensor A and Sensor B (at approximate 
five-second intervals).
For example: Load 1: Compressor 1 (cool)
Setpt 1
On at
Diff 1
Off at
For example: Load 1: Compressor 1 (cool)—Sensor A
Setpt 1
On at
Diff 1
Off at
For example: Load 1: Compressor 1 (cool)—Sensor A
Setpt 1
78°F
On at
Diff 1
4°F
Off at
For example: Load 1: Compressor 1 (cool)—Sensor A
Setpt 1
78°F
On at
82°F
Diff 1
4°F
Off at
78°F