T775A,B,C,D REMOTE TEMPERATURE CONTROLLER
7
63-2489—2
OPERATION
Control Algorithm
On/Off Control
The T775AC operate with one temperature input supplied by 
the remote sensor while T775B,D have two temperature 
inputs. The T775A,B,C,D are all capable of providing up to four 
stages of on/off control relay outputs. Each controller stage has 
its own independent setpoint that can be configured to operate 
in either the heating or cooling mode. The mode of operation 
for each stage is user-determined by programming keys.
Heating Mode Operation
• Relay outputs energize at the temperature setpoint minus 
the differential value.
• Relay outputs de-energize at the temperature setpoint 
value.
Cooling Mode Operation
• Relay outputs energize at the temperature setpoint plus 
differential value.
• Relay outputs de-energize at the temperature setpoint 
value.
EXAMPLE
Using a device with one input and one relay output, the 
corresponding load energizes at the following temperatures 
based on the initial settings:
• Setpoint: 68°F
• Differential: 2°F
Outputs Energized
Heating Mode: Stage One energizes at 66°F.
Cooling Mode: Stage One energizes at 70°F.
The T775B,D have dual sensor inputs and allow two separate 
controllers to exist within one enclosure. Selection of the stage 
parameters (operation mode, setpoints, and differentials) is the 
same as for a single sensor device after each stage is 
assigned its operating sensor. This assignment is hardware 
driven via a four position DIP switch. An explanation of the DIP 
switch assignments appears in Fig. 9. See Fig. 3 and 4 for the 
DIP switch location.
Contact Closure Override Input
The two-terminal input allows the user to override a relay-
energized condition on all outputs. This is done using contact 
closure between terminal pins 3 and 4 (TOD). (See Fig. 3 an
for location.) This can be achieved manually or by using an 
EMS controller or time clock with normally open contacts 
(W7505 or S7005, for example).
When this override is active:
— The display shows the number of stages that would be 
energized
— The words STAGE ENERGIZED flash on the display.
— Energized stages de-energize until the override returns to 
inactive (Off).
°F/°C Selection
A single jumper plug controls °F/°C indication of the displayed 
temperature value. See Fig. 3 and 4 for the location of this 
jumper. The unit ships with the jumper installed in the °F mode. 
To operate the device in the °C mode, remove the jumper. 
Replacing the jumper reinstates the °F mode.
NOTES: If, upon removing the jumper plug, the device does 
not display °C:
Remove power from the device.
Replace power to the device.
DIP Switch Selections
On the T775B,D, DIP switches are provided for assignment of 
each relay output stage to its operating sensor. If an individual 
switch is depressed to the right—toward its corresponding load 
number (1 through 4 on DIP switch)—Sensor B is the 
controlling sensor for that output stage. If an individual switch 
is depressed to the left, Sensor A is the controlling sensor for 
the output stage. An example of the switches and their 
corresponding positioning is shown in Fig. 9.
Fig. 9. DIP switch settings for sensor selection.
Device Setup
1. Determine loads to be controlled and the operating mode 
(heat or cool) and enter them in the Device Programming 
Worksheet (Table 2).
Table 2. Device Programming Worksheet.
Load 1:
SetPt 1
On at
Diff 1
Off at
Load 2:
SetPt 2
On at
Diff 2
Off at
Load 3:
SetPt 3
On at
Diff 3
Off at
Load 4:
SetPt 4
On at
Diff 4
Off at
M3292
LOAD 1 IS CONTROLLED BY 
SENSOR A WHEN SWITCH IS 
DEPRESSED ON THE LEFT
LOAD 2 IS CONTROLLED BY 
SENSOR B WHEN SWITCH IS 
DEPRESSED ON THE RIGHT 
(AS SHOWN)
SENSOR A
SENSOR B
LOAD 1
LOAD 2
SIDE VIEW
A
B
SWITCH
SWITCH
PWB
PWB