The thermostat uses a red LED indicator that lights when the 
thermostat is in the Emergency Heat mode. The LED is located 
in the upper right corner of the thermostat. It is visible only 
when on.
Heat Pump Temperature Lockouts
Dual Fuel Heat Pump and Outdoor Temperature 
Sensor
In this operation, there is no external fossil fuel kit (dual fuel kit) 
installed; the thermostat controls this function.
1. Choose correct heat pump application in Installer Setup 
Number 0172.
2. Choose Fossil Fuel Option as the backup heat source 
in Installer Setup Number 0200.
3. Choose No External Fossil Fuel Kit Option is control-
ling back up heat in Installer Setup Number 0210.
4. Choose Outdoor Temperature Sensor for Heat Pump 
Temperature Lockouts in Installer Setup Number 0342.
5. Choose appropriate Balance Point Temperature in 
Installer Setup Number 0350.
Dual Fuel Heat Pump Control
Balance Point Only (ISU345 = 0)
NOTE: System must have an outdoor temperature sensor.
When the outdoor temperature is above the selected balance 
point temperature, only the compressor operates and the fan 
(G terminal) energizes when the thermostat calls for heat. See 
Fig. 30. When the outdoor temperature is below the selected 
balance point temperature, only the fossil fuel (auxiliary heat) 
operates and the fan (G terminal) does not energize when the 
thermostat calls for heat.
Fig. 30. Dual Fuel Heat Pump Operation in Heat mode with 
Balance Point Set.
Balance Point Plus 2° Droop (ISU345 = 1)
The fossil fuel will turn on when the outdoor temperature is 
above the balance point if the room temperature droops 
approximately 2 degrees below the temperature setting, and 
the compressor will be disabled.
Balance Point/Auxiliary Heat Lockout Plus 2° Droop 
(ISU 345 = 2)
When the outdoor temperature is above the Auxiliary Heat 
Lockout Temperature only the compressor operates; below the 
balance point temperature (setup function 0360) only the fossil 
fuel operates. Between the balance point temperature and 
auxiliary heat lockout temperature the compressor will operate. 
However, the fossil fuel will turn on if the room temperature 
droops approximately 2°F below the temperature setting, 
compressor will be disabled.
Fig. 31. Balance Point with Auxiliary Lockout Temperature.
AUXILIARY LOCKOUT FOR ELECTRIC HEAT BACKUP
Heat Pump systems with electric heat backup can select a 
compressor lockout temperature (function 0350) and/or 
auxiliary heat lockout temperature (function 0360). When the 
outdoor temperature is below the compressor lockout 
temperature, only the auxiliary heat operates. When the 
outdoor temperature is between the compressor and auxiliary 
lockout temperatures, both the compressor and auxiliary heat 
can operate.
NOTE: System must have an outdoor temperature sensor.
Heat Pump with Electric Auxiliary (Backup) Heat and 
Outdoor Temperature Sensor
1. Choose correct heat pump application in Installer Setup 
Number 0172.
2. Choose Electric as Auxiliary (Backup) Heat Source in 
Installer Setup Number 0200.
3. Choose Outdoor Temperature Sensor in Installer 
Setup Number 0342.
4. Choose Compressor Lockout Temperature in Installer 
Setup Number 0350.
5. Choose Auxiliary Lockout Temperature in Installer 
Setup Number 0360.
NOTE: There is a 5°F deadband between the Compressor 
and Auxiliary Heat Lockout Temperatures.
Operation in Heat Mode
When the outdoor temperature is below the Compressor 
Lockout Temperature, only the Auxiliary Heat operates.
When the outdoor temperature is above the Auxiliary Lockout 
Temperature, only the Compressor operates. See Fig. 32.
30
M22441
BALANCE
POINT
COMPRESSOR ONLY
FOSSIL FUEL ONLY
OUTDOOR TEMPERATURE
50
35
OUTDOOR TEMP
ERATURE
BALANCE
POINT
AUX.
LOCKOUT 
COMPRESSOR ONLY
COMPRESSOR+2 °F
DROOP UPSTAGE TO
FURNACE 
FURNACE ONLY
M23497