Honeywell THM5421C1008 Benutzerhandbuch

Seite von 40
VISIONPRO
®
 IAQ TOTAL HOME COMFORT SYSTEM
68-0287—1
32
NOTE: It takes about a week for the thermostat to adjust to 
local weather, the schedule, the construction of the 
home and the heating and/or cooling system. Each 
day it adjusts the next day’s recovery start time 
accordingly.
P+I Control
The thermostat microprocessor-based control requires that the 
user understands temperature control and thermostat 
performance. A conventional mechanical or electronic 
thermostat does not control temperature precisely at setpoint. 
Typically there is an offset (droop) in the control point as the 
system load changes. This is a phenomenon that most people 
in the industry know and accept. Many factors contribute to 
offset including switch differential, thermal lag, overshoot, cycle 
rates and system load.
The thermostat microprocessor simultaneously gathers, 
compares and computes data. Using this data, it controls a 
wide variety of functions. The special proprietary algorithm 
(program) in the thermostat eliminates the factors causing 
offset. This makes temperature control more accurate than the 
conventional mechanical or electronic thermostats. The 
temperature control algorithm is called proportional plus 
integral (P+I) control.
The thermostat sensor, located on the thermostat or remote, 
senses the current space temperature. The proportional error 
is calculated by comparing the sensed temperature to the 
programmed setpoint. The deviation from the setpoint is the 
proportional error.
The thermostat also determines integral error, which is a 
deviation based on the length of error time. The sum of the two 
errors is the (P+I) error. The cycle rate used to reach and 
maintain the setpoint temperature is computed using the P+I. 
The addition of the integral error is what differentiates the 
thermostat from many other electronic and mechanical 
thermostats. See Fig. 33.
Fig. 33. Proportional temperature control versus P+ I 
temperature control.
Minimum Off-Timer
The Thermostat has built-in compressor protection (minimum-
off timer) that prevents the compressor from restarting too 
early after a shutdown. The minimum-off timer is activated after 
the compressor turns off.
If there is a call during the minimum-off timer, the thermostat 
shows “Wait” in the display.
When the minimum-off timer expires, “Cool On” or “Heat On”
a
 
appears in the display and the compressor and fan turn on.
_________
a
Heat Pumps only.
Inside Humidity Level
The humidity level in the home is shown in the lower right 
corner of the Home Screen.
NOTE: If an outdoor temperature sensor is present, the out-
door temperature will be displayed in this location 
rather than the indoor humidity. To see indoor humid-
ity, display the humidity settings menu.
If thermostat is set to Auto Changeover System mode, press 
the More key until the humidity level is shown on the screen.
HEATING
COOLING
PERCENT LOAD
TEMPERATURE
THERMOSTAT
HEAT SETPOINT
P+I CONTROL
POINT
PROPORTIONAL COOL 
CONTROL POINT
THERMOSTAT 
COOL SETPOINT
P+I CONTROL POINT
PROPORTIONAL HEAT 
CONTROL POINT
M4414
100
50
0
50
100
M23513 
Wait 
SCHED HOLD CLOCK SCREEN 
MORE 
WED 
AM
 
PM 
FAN 
 
AUTO 
SYSTEM 
HEAT
 
COOL
Following 
Schedule 
Inside 
Set To 
Humidity 
 
SCHED HOLD CLOCK 
SCREEN MORE 
TUE 
PM 
FAN 
 
AUTO 
SYSTEM 
 
COOL 
Following 
Schedule 
Inside 
Set 
 
Humidity 
M23678