Honeywell T7350 Benutzerhandbuch

Seite von 40
T7350 COMMERCIAL PROGRAMMABLE THERMOSTAT
63-2605—5
20
Fig. 13. Setpoint ramping parameters with ramp rate 
calculation.
NOTE: The setpoint used during the cool recovery period is 
similar to the heat mode in Fig. 11, except the slope 
of the line reverses for cooling.
Advantages:
• Comfort setting is achieved at the programmed time and 
maintained regardless of weather conditions; occupants 
are comfortable.
• Drafts from low-temperature discharge air are minimized 
during Occupied periods.
• Use of the more economical first stage of heat is 
maximized during recovery, minimizing use of the 
expensive later heat stage(s).
• Comfort and energy savings can be achieved in both 
heating and cooling.
• Heat cycling reduced, extending equipment life.
Auxiliary Relay
The auxiliary relay can be used with a variety of controls:
• Time-of-day (TOD).
• Economizer minimum position control.
• Dehumidification (see Dehumidification section).
Time-of-day (TOD) is the Auxiliary Relay default configuration. 
TOD logic operates strictly according to programming:
— Occupied: Relay contacts closed.
— Not Occupied: Relay contacts open.
— Standby (Scheduled): Relay contacts closed.
Relay for Economizers
Mechanical cooling is often used with outside temperatures in 
the 50°F (10°C) to 60°F (16°C) range and humidity below 50 
percent. In central and northern climates, hundreds of hours 
fall into this temperature category. By permitting 80 to 100 
percent outside air into the system, mechanical cooling may 
not be needed at all, particularly during Spring and Fall.
Economizers take advantage of outside air. The typical 
economizer consists of an outside air damper, motor, outdoor 
air changeover control and a minimum position potentiometer. 
The motor controls the dampers. Suitability of the outside air 
for cooling is determined by the outdoor air changeover 
control. The potentiometer adjusts the minimum position of 
the economizer dampers, which provide a minimum amount 
of fresh air for ventilation.
The economizer reduces compressor run time, thereby saving 
energy and extending compressor life. The drawback to using 
the economizer is that during the Not Occupied period, if there 
is no call for cool or outdoor air is not suitable for free cooling, 
the economizer is controlled to minimum position. This 
position allows some percentage of outdoor air to enter the 
building, regardless of air suitability. The situation can cause 
the heating or cooling to run more often than when only 
suitable air is permitted to enter the building.
The T7350 can take advantage of an economizer by closing 
the auxiliary relay contacts to control the economizer 
minimum position potentiometer. (See Table 16 for details.)
— Powered: Allows normal economizer operation.
— Unpowered: Disables the economizer minimum position. 
The lack of power causes the economizer to drive dampers 
fully closed instead of staying at minimum open position. 
This reduces the possibility of unsuitable outdoor air 
entering the building, which lowers the internal load on the 
HVAC system and saves additional energy.
Table 16. Auxiliary Relay Logic (Economizer and TOD).
a
Unless otherwise noted, Economizer logic ignores calls for 
heat. TOD logic always observes calls for heat.
b
With fan set to AUTO and call for neither heat nor cool, the 
relay is open in order to disable damper minimum position.
Other Uses for the Auxiliary Relay
Examples of other uses of the auxiliary relay are hot water 
heaters, lighting, or baseboard heat. The additional loads are 
connected to the auxiliary relay contacts on the subbase. The 
contacts are rated for 1.5A at 30 Vac, but can be adapted to 
higher current applications using an external relay. 
COOL RECOVERY 
RAMP RATE
(DEGREES/HOUR)
MaxClRamp
MinClRamp
OaTempMinClRamp
OaTempMaxClRamp
OUTDOOR AIR
TEMPERATURE
M10111A
Occupancy
Call for
 Cool
a
Auxiliary Contacts
Scheduled Sensor Signal
Economizer
TOD
Occupied
 
Closed
b
Closed
 
Occupied
Standby
Yes
Closed
Open
Occupied
Standby
No
Open
Open
Standby
 
Standby
 
Closed
b
Closed
Not Occupied
Yes
Closed
Open
Not Occupied
No
Open
Open