Honeywell T7350 Benutzerhandbuch

Seite von 40
T7350 COMMERCIAL PROGRAMMABLE THERMOSTAT
63-2605—5
22
Dehumidification (T7350D,M,H only)
There are five methods through which the T7350 can control 
for dehumidification. Three of them modify the control 
algorithm, thus providing limited dehumidification through 
cooling. The other two use the auxiliary output to control 
another device.
IMPORTANT
Configurable only with a PDA or a network tool such 
as LonSpec or CARE.
NOTE: The dehumidification high limit can be set within the 
range of 10 to 90 percent relative humidity.
Control Through Cooling
Configure using some combination of the following:
— Minimum On.
— Reheat.
— Reset.
NOTES:
These methods operate only during cooling.
Selecting both Reheat and Reset can cause 
frequent setpoint adjustments. This selection 
is not recommended.
MIN ON TIME
Dehumidifies by increasing the compressor minimum on time 
(normally 3 minutes) by a programmable amount. This is 
useful with oversized systems in that it forces the coils to cool 
to a point where dehumidification can occur.
NOTES:
Can force wider temperature swings by cooling 
when setpoint control does not require it.
The minimum on time can be set within the range 
of 5 to 15 minutes.
Hysteresis and a minimum timer are used to 
ensure this behavior does not change with every 
equipment cycle.
REHEAT
Dehumidifies by operating cooling during typical off time. The 
T7350 maintains the proper setpoint by running the heat at the 
same time.
IMPORTANT
At times during Reheat dehumidification, the T7350 
operates heating and the cooling simultaneously. 
This is normal.
NOTES:
The heat stage never energizes during Reheat if 
more than one cool stage is on.
Reheat mode cannot occur during heating.
The T7350H1017, T7350M do not support the 
Reheat method.
RESET TEMP SETPT
The room temperature set point resets to a specified number 
of degrees below the actual set point when room relative 
humidity (RH) rises above humidity high limit.
Though this may not technically reduce RH, it reduces the 
dew point to provide the customer with a sense of comfort due 
to a lower temperature setting in the room.
As long as RH stays above humidity high limit, this set point is 
maintained.
NOTE: Hysteresis and a minimum timer prevent the set 
point from short interval alternation (between stan-
dard and reset set points).
Options Utilizing Auxiliary Output
There are two dehumidification options that utilize the 
auxiliary output. They are:
— Simple Dehumidification.
— Hot Gas Bypass Dehumidification.
SIMPLE DEHUMID(IFICATION)
The auxiliary output:
— Energizes when RH rises above humidity high limit.
— De-energizes when RH drops below humidity high limit.
NOTES:
Hysteresis and a minimum timer prevent short 
cycling of this output.
Unlike Dehumid Hot Gas BP the relay remains 
energized during calls for multiple cooling stages.
DEHUMID HOT GAS BP
The auxiliary output operates as shown in Table 18.
Table 18. Hot Gas Bypass Dehumidification Logic.
Auxiliary output during call for multiple cooling stages for two 
reasons:
1. This method assumes that the cooling provides dehu-
midification.
2. Multiple cooling stages probably provide necessary 
dehumidification.
NOTE: Hysteresis and a minimum timer prevent short 
cycling of this output.
Humidity
Cooling Stages Active
Auxiliary Output
High
more than one
De-energized
High
one or less
Energized
Low
more than one
De-energized
Low
one or less
De-energized