  The exhaust from this product gets extremely 
hot and remains hot after shutdown. High grass, 
weeds, brush, leaves, etc. must remain clear of the 
exhaust. Such materials may ignite and burn from 
the heat of the exhaust system.
  The maximum ambient temperature for the 
generator is 48.9° C (104° F).
4.10  ATTENTION AFTER SUBMERSION
If the generator has been submerged in water, it 
MUST 
NOT be started and operated. Following any submersion 
in water, have an Authorized Dealer thoroughly clean and 
dry the generator.
4.11  CORROSION PROTECTION
Periodically wash and wax the enclosure using automo-
tive type products.  Frequent washing is recommended 
in salt water/coastal areas.  Spray engine linkages with 
a light oil such as WD-40.
4.12  OUT OF SERVICE PROCEDURE
4.12.1  REMOVAL FROM SERVICE
If  the  generator  cannot  be  exercised  every  seven  days, 
and it is to be out of service longer than 90 days, pre-
pare the generator for storage as follows:
1.  Start the engine and let it warm up.
2.  Close  the  fuel  shutoff  valve  in  the  fuel  supply  line 
and allow the unit to shut down.
3.  Once the unit has shut down, it will signal a low oil 
fault.
4.  Set the AUTO/OFF/MANUAL switch to OFF and turn 
off the utility power to the transfer switch.
5.  While the engine is still warm from running, drain 
the oil completely. Refill the crankcase with oil. See 
”Engine Oil Recommendations,” Section 4.3.1.
6.  Attach  a  tag  to  the  engine  indicating  the  viscosity 
and classification of the oil in the crankcase.
7.  Remove  the  spark  plug(s)  and  spray  fogging  agent 
into the spark plug(s) threaded openings. Reinstall 
and tighten the spark plug(s).
8.  Remove the battery and store it in a cool, dry room 
on a wooden board. Never store the battery on any 
concrete or earthen floor.
9.  Clean and wipe the entire generator.
4.12.2  RETURN TO SERVICE
To  return  the  unit  to  service  after  storage,  proceed  as 
follows:
1.  Set the generator’s main circuit breaker to its OFF 
(or open) position.
2.  Verify  that  utility  power  is  turned  off  and  that  the 
AUTO/OFF/MANUAL switch is set to OFF.
3.  Check  the  tag  on  the  engine  for  oil  viscosity  and 
classification. Verify that the correct recommended 
oil is used in the engine (see Section 4.3.1). If neces-
sary, drain and refill with the proper oil.
4.  Check the state of the battery. Fill all cells of unsealed 
batteries to the proper level with distilled water. DO 
NOT USE TAP WATER IN THE BATTERY. Recharge 
the  battery  to  100  percent  state  of  charge,  or,  if 
defective,  replace  the  battery.  See  “Specifications,” 
Section 1.5, for type and size.
5.  Clean and wipe the entire generator.
6.  Remove  the  5A  fuse  from  the  generator  control 
panel.
7.  Reconnect  the  battery.  Observe  battery  polarity. 
Damage may occur if the battery is connected incor-
rectly. Replace the 5A fuse in the generator control 
panel.
8.  Open the fuel shutoff valve.
9.  Start  the  unit  by  moving  the  AUTO/OFF/MANUAL 
switch to MANUAL. Allow the unit to warm up thor-
oughly.
10. Stop  the  unit  and  set  the  AUTO/OFF/MANUAL 
switch  to  AUTO.  Set  the  generator’s  main  circuit 
breaker to its ON (or closed) position.
11. Turn on the utility power to the transfer switch.
12.  The generator is now ready for service.
NOTE:
If the battery was dead or disconnected, the exercise 
timer must be reset.
Section 4 — Maintenance
Air-cooled 7 kW, 12 kW and 15 kW Generators