Part # 25000102
Installation and Operations Manual
AC&R
Model
No.
Connection
Size
Operation
Pressure
Diff., psig
Oil Level,
Sight Glass
S-9010
3 BOLT
5 - 30
1/2
S-9010A
4 BOLT
5 - 30
1/2
S-9015
3/4” NPTF F.
5 - 30
1/2
S-9090
3 BOLT
5 - 90
Adjustable
S-9090A
4 BOLT
5 - 90
Adjustable
S-9110
3 BOLT
5 - 30
1/2
S-9120
3 BOLT
5 - 30
1/4 +
S-9130
3 BOLT
5 - 90
Adjustable
S-9190
3 BOLT
30 - 90
Adjustable
Sporlan
Model
No. Of
Cores
Desiccant
Volume
(cu. in.)
# Core
Part No.
C-489-(G)
1
48
RC-4864
RC-4864-HH
RCW-48
C-969-(G)
2
96
C14411-(G)
3
144
C-19211-(G)
4
192
C-4021-(G)
4
192
C-4025-(G)
4
192
Troubleshooting Oil System
The oil return line should always be checked. Feeling the oil 
return line and seeing how often it gets hot is the main way to 
tell if the separator is working properly. It is easier if an oil line 
sight glass is installed, mainly because if the oil line is hot you 
don’t know if it is oil or hot gas causing it to be hot. If the oil 
line cycles between hot and cold at least a few times per hour, 
the separator is most likely working properly. The float tends to 
open and feed a few ounces of oil at a time and shut until the 
oil builds back up. If the oil return is cycling there is no need to 
drain the separator to look at the float components.
Always check the oil reservoir level during a service call. Oil 
levels in the reservoir will normally vary during periods of 
varying loads: compressors shutdown, hot-gas defrost, etc. This 
is normal, however if the level is consistently low or high, the 
oil system should be checked thoroughly.
Compressor oil levels can be deceiving. It is sometimes hard 
to tell if the regulator is feeding oil or if oil is coming down the 
suction line. If the reservoir has too much pressure, often times 
this pressure will force oil out of the regulator and show a low 
level, even though there may be excessive oil in the compressor. 
Many times the best way to check the oil in the compressor is to 
shut off the oil feeding to the regulator while the compressor 
is operating and wait a few minutes. If oil is pushed out of the 
regulator or trapped in the motor cavity on semi-hermetic 
models, the compressor will overfill.
The oil line sight glass is a good way to see how the separator is 
working. Look for movement in the glass. If the separator is not 
feeding on single or low pressure systems, the sight glass will 
have little or no movement and normally will appear empty. If 
the separator is feeding, the sight glass will show a rush of oil 
and foam past the glass. Most of the time, viewing this sight 
glass can prevent having to open the system.
To check the oil level in the separator if the separator has a drain, 
shut off the oil return line to prevent further feeding, pump 
down the system, shut off the system, evacuate the separator, 
and drain the oil from the bottom.
The separator should hold the pre-charge amount plus or minus 
a few  ounces during operation. By looking at the amount above 
or below the pre-charge, any problem with the separator or 
float can be determined.
Note that there is no way to clean or repair welded oil separators. 
If  it  is  determined  that  the  float  is  clogged  or  otherwise 
malfunctioning, the entire oil separator must be replaced.
When the refrigerant and/or oil types are changed in a system, 
there  is  the  potential  for  leaks  around  o-ring  seals.  Most 
elastomers absorb oil and refrigerant and may swell or shrink 
when exposed to a new oil or refrigerant. In these cases replace 
the o-rings and seals in the system as needed.
Liquid Filter-Driers & Suction Filters
A replaceable core liquid filter/drier is supplied as standard 
on all Rack units and is an option in all other parallel systems. 
A Schrader type access valve is installed in the flange plate of 
some models. The liquid cores are always shipped loose for 
field installation. (See No. 5 of Leak Checking, Evacuation,  and 
Start-up section in this manual).
Table 22. AC&R Model Regulators
Table 23. Sporlan Valve Co.
Table 24. Alco Controls
“G” indicates flange plate supplied with _” FPT
#  “RC__” Standard Core, “RC__HH” Burnout Core
 “RCW_” High Water Capacity
* “T” indicates Liquid Line Service
#  “D” Standard Capacity, “H” High Capacity
 ”UK” High Capacity, “W” Burnout Block
Alco
Model
No. Of
Cores
Desiccant
Volume
(cu. in.)
# Core
Part No.
STAS-489-T*
1
48
D-48
H-48
UK-48
W-48
STAS-969-T
2
96
STAS-14411-T
3
144
STAS-19211-T
4
192
STAS-19213-T
4
192
STAS-19217-T
4
192