APC 990-3051C-001 Benutzerhandbuch
990-3051C-001
12/2009
Installation
Modular Rack-Mount Power
Distribution Unit
IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS
This manual contains important instructions for the modular rack-mount
Power Distribution Unit (PDU) that should be followed during
installation and maintenance of this unit.
Power Distribution Unit (PDU) that should be followed during
installation and maintenance of this unit.
Handling Safety
Heavy: To prevent back injury, two or more people are
required to install the PDU in a rack.
required to install the PDU in a rack.
Electrical Safety
Warning: To reduce risk of electric shock or injury to
persons, disconnect all sources of power before servicing.
persons, disconnect all sources of power before servicing.
Note: Install the unit in accordance with the National and
Canadian Electrical Codes, and if applicable, local codes.
Canadian Electrical Codes, and if applicable, local codes.
Note: To prevent arcing when removing an APC
Power Distribution Module (PDM) from the PDU,
set all PDMs to
Power Distribution Module (PDM) from the PDU,
set all PDMs to
OFF
. Do not remove the modules
under load.
Inventory
How to perform a Total Power Off
1
Set all the APC Power Distribution Modules (PDM) to the
OFF
position.
2
Set the utility/mains circuit breaker to the
OFF
position.
3
If the utility/mains is an UPS, set the UPS and its circuit breaker
supplying this product to the
supplying this product to the
OFF
position.
4
Disconnect the input conductors from the utility/mains or the UPS.
Installation
How to install the PDU
1
Install the mounting rails in the enclosure by using the screws
provided. The PDU requires a 5U space from the top of the
enclosure.
2
Slide the support tray into the mounting rails and secure it with the
screws provided.
3
Slide the PDU on to the support tray and secure it to the front posts of
the enclosure with the screws provided.
the enclosure with the screws provided.
4
Slide the bracket tie-downs onto the guide pins on the side of the
PDU and secure the tie-downs to the back posts of the enclosure with
the screws provided.
PDU and secure the tie-downs to the back posts of the enclosure with
the screws provided.
Item
Part Number
Quantity
Modular rack-mount PDU 138 KW
200 A 400 V 18 Pole 5U
200 A 400 V 18 Pole 5U
0G-PDPM138H-5U
and
0G-PDPM72F-5U
and
0G-PDPM72F-5U
1
Literature kit rack-mount PDU
0L 1532
1
Label kit rack-mount PDU
0M-8909
Rail stationary black
870-8197D-001
2
Rail adjustable black
870-8198D-001
2
Tray support chassis rack-mount PDU
870-14067
1
Screw M6x12 phil flat head
803-0608
6
Nut M6 flanged hex
803-2406A
6
Washer M6 black plastic cup
803-0009B
14
Screw M6x16 phillips/slot
803-0616B
14
Nut cage M6 14/16 swg
803-0006A
6
Bracket tie-down rear rack-mount PDU
870-14158
2
Plate blank cover brain PCB
870-14159
1
5 U
pd
x0
24
4a
1
p
dx
02
40
a
2
pd
x0
2
42
a
3
4