APC 990-3051C-001 User Manual

Page of 4
990-3051C-001
12/2009
Installation
Modular Rack-Mount Power
Distribution Unit
IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS
This manual contains important instructions for the modular rack-mount 
Power Distribution Unit (PDU) that should be followed during 
installation and maintenance of this unit. 
Handling Safety
Heavy: To prevent back injury, two or more people are 
required to install the PDU in a rack.
Electrical Safety
Warning: To reduce risk of electric shock or injury to 
persons, disconnect all sources of power before servicing.
Note: Install the unit in accordance with the National and 
Canadian Electrical Codes, and if applicable, local codes.
Note: To prevent arcing when removing an APC 
Power Distribution Module (PDM) from the PDU, 
set all PDMs to 
OFF
. Do not remove the modules 
under load.
Inventory
How to perform a Total Power Off 
1
Set all the APC Power Distribution Modules (PDM) to the 
OFF
 
position.
2
Set the utility/mains circuit breaker to the 
OFF
 position.
3
If the utility/mains is an UPS, set the UPS and its circuit breaker 
supplying this product to the 
OFF
 position.
4
Disconnect the input conductors from the utility/mains or the UPS.
Installation
How to install the PDU
1
Install the mounting rails in the enclosure by using the screws 
provided. The PDU requires a 5U space from the top of the 
enclosure.
2
Slide the support tray into the mounting rails and secure it with the 
screws provided.
3
Slide the PDU on to the support tray and secure it to the front posts of 
the enclosure with the screws provided. 
4
Slide the bracket tie-downs onto the guide pins on the side of the 
PDU and secure the tie-downs to the back posts of the enclosure with 
the screws provided. 
Item
Part Number
Quantity
Modular rack-mount PDU 138 KW
200 A 400 V 18 Pole 5U
0G-PDPM138H-5U 
and 
0G-PDPM72F-5U
1
Literature kit rack-mount PDU
0L 1532
1
Label kit rack-mount PDU
0M-8909
Rail stationary black 
870-8197D-001
2
Rail adjustable black
870-8198D-001
2
Tray support chassis rack-mount PDU
870-14067
1
Screw M6x12 phil flat head
803-0608
6
Nut M6 flanged hex
803-2406A
6
Washer M6 black plastic cup
803-0009B
14
Screw M6x16 phillips/slot
803-0616B
14
Nut cage M6 14/16 swg
803-0006A
6
Bracket tie-down rear rack-mount PDU
870-14158
2
Plate blank cover brain PCB
870-14159
1
5 U