FLUE SYSTEMS
Figure 11A - Chimney Connector
FLUE 
GAS
 DIRECTION
CRIMPED 
END 
TOWARDS 
STOVE
T
here are two separate and different parts to a flue system: the 
chimney connector and the chimney itself.
1.  Single wall connector or stovepipe.  This must be at least 
24 gauge mild steel or 26 gauge blue steel.  The sections 
must be attached to the stove and to each other with the 
crimped (male) end pointing toward the stove. 
 See Figure 
11A.  All joints, including the connection at the stove collar, 
should be secured with three sheet metal screws.  Make 
sure to follow the minimum clearances to combustibles as 
set out on 
pages 6 and 7 of this manual. Where passage 
through the wall, or partition of combustible construction 
is  desired,  the  installation  shall  conform  to  CAN/CSA-
B365.
2.  Factory-built listed chimney connector (vented).  A listed 
connector (vented) must be used when installing this unit 
in a mobile home.  A listed chimney and listed connector 
must be used.  they must conform to each other to ensure 
a proper fit and seal.
MASONRY CHIMNEY
Figure 11B
For optimal performance, masonry chimneys used to vent this 
appliance should be lined with a 6 inch stainless steel liner.  
Installations into a clay flue without a stainless steel liner may 
reduce  efficiency,  cause  the  glass  to  darken,  and  produce 
excessive creosote.
Ensure that a masonry chimney meets the minimum standards 
of the National Fire Protection Association (NFPA) Standard 
211. It must have at least a 5/8 inch (16mm) fire clay liner or 
a listed chimney liner system. 
See Figure 11B. Make sure 
there are no cracks, loose mortar or other signs of deteriora-
tion and blockage.  It is best to have the chimney inspected 
by a professional and be sure to have the chimney cleaned 
before the stove is installed and operated. 
The flue should be checked to determine that it is
 
not 
t
oo large 
for the stove.  NFPA 211 allows the cross-sectional area of 
the flue to be no more than 3 times the cross-sectional area 
of the flue collar of the stove (28 x 3 = 84 square inches).  It 
is recommended that a chimney with a larger diameter be 
relined, since the oversized flue can cause poor performance 
and contribute to the accumulation of creosote.  (See 
page 10 
for more information about troubleshooting draft problems).  
CAUTION! DO NOT CONNECT THIS UNIT TO A
 CHIMNEY FLUE SERVING ANOTHER APPLIANCE. 
When connecting the stove through a combustible wall to a 
masonry chimney, special methods are needed.  There are 
several ways to make this connection, including the construc-
tion of a masonry thimble.  This installation shall conform to 
CAN/CSA-B365.  Check with your local building authorities 
or  consult  the  National  Fire  Protection Association  (NFPA 
211).  Refer to 
Figure 12B (page 12) and Figures 13A & 
13B (page 13).
WARNING!  IF INSTALLING THIS MODEL TO A MASONRY CHIMNEY, ALWAYS BE SURE THE CHIMNEY IS IN GOOD CONDITION AND THAT IT 
MEETS THE MINIMUM STANDARDS OF THE NATIONAL FIRE PROTECTION ASSOCIATION (NFPA) STANDARD 211.
THIS APPLIANCE IS MADE WITH A 6 INCH/152mm DIAMETER CHIMNEY CONNECTOR AS THE FLUE COLLAR ON THE UNIT. CHANGING 
THE  DIAMETER  OF  THE  CHIMNEY  CAN AFFECT  DRAFT AND  CAUSE  POOR  PERFORMANCE.    IT  IS  NOT  RECOMMENDED  TO  USE 
offSetS or elbowS at altitudeS aboVe 4000 feet aboVe Sea leVel or when there are other factorS that affect 
FLUE DRAFT.