FLOOR PROTECTION
The floor must be non-combustible material, extending beneath heater and to the front, sides and rear as indicated.  The 
floor must be non-combustible or otherwise adequately protected from radiant heat given off by the unit and from sparks 
and falling embers.  A layer of thin brick or ceramic tile over a combustible floor is not sufficient.  See Alternate floor protec-
tion calculation sample on 
page 8.
In USA installations, it is necessary to install a floor protector 16 inches in front and 8 inches to both sides of the loading 
door. 
See *exception below.
In Canada, similar floor protection must be provided 18 inches (457mm) in front and 8 inches (203mm) from the sides and 
rear of the stove.  
See *exception below.
*ExCEPTION:  Non combustile floor protections must extend beneath the flue pipe when installed with horizontal venting 
and extend 2 inches (51mm) beyond each side. 
CANADA
203mm (8")
203mm
(8")
203mm
(8")
457mm (18")
1251mm 
(49-1/4")
Minimum
1137mm (44-3/4")
Minimum
16" from glass - std legs 
8" 
USA 
Fuel loading door 
36-3/4" 
Minimum 
39-1/4" 
Minimum 
must extend 
length of flue and 
2" (51mm) 
beyond each 
side of pipe
USA - Required
CANADA - Recommended
16"
optional coverage
optional
coverage
optional
coverage
8”
36-9/16"
required 
coverage
38-5/8"
51"
30-3/8"
51"
USA Installations
fuel loading door