A range cord rated at 40 amps with 
125/250 minimum volt range is required. 
A 50 amp range cord is not recommended 
but if used, it should be marked for use with 
nominal 1
3
/
8
" diameter connection openings. 
Care should be taken to center the cable 
and strain relief within the knockout hole to 
keep the edge from damaging the cable.
• Because range terminals are not accessible 
after range is in position, flexible service 
conduit or cord must be used.
 NOTE
If conduit is being used, go to Step 5 on 
page 32 ~ 34.
ALL NEW BRANCH-CIRCUIT 
CONSTRUCTIONS, MOBILE 
HOMES, RECREATIONAL 
VEHICLES AND INSTALLATIONS 
WHERE LOCAL CODES DO NOT ALLOW 
GROUNDING THROUGH NEUTRAL, REQUIRE 
A 4-CONDUCTOR UL-LISTED RANGE CORD.
Step 3. Accessing the power cord connection
Remove the rear access cover and loosen the screw with a screwdriver. The terminal block 
will then be accessible.
Access cover
Terminal block
Specified power-supply-cord kit rating
Range rating, watts
Specified rating of 
power-supply-cord kit, 
amperes
Diameter (inches) of range 
connection opening
120/240 volts 
3-wire
120/208 volts 
3-wire
Power cord
Conduit
8750 - 16500
7801 - 12500
40 or 50A
1
3
/
8
"
1
1
/
8
"