Honeywell CM921 Benutzerhandbuch

Seite von 7
CM921 CHRONOTHERM
 
 
 
3
EN0H 8557 UK07 R0 09/06 
INSTALLER SET-UP 
In Installer set-up we can:
 
❑  Set-up specific applications parameters 
❑  Enable special features 
❑  Configure system timing master for the zoning system 
To enter the installer set-up mode:
a)  Move the slider switch to the OFF position. 
b)  Press and hold the INFO 
i
 button and the two program 
buttons ‘< >’ together.  
c)  The unit will display the first parameter of installer 
parameter group category 1 (from n.1 to n.19). 
d) Press the TEMP 
 or 
 buttons 
to change the factory 
setting. The display will flash indicating that a change has 
been made. 
e)  Press the green OK button to confirm this change and the 
display will stop flashing. 
f) Press 
the   + button to go to the next parameter. 
g)  Press the program button 
>
 to go to category 2 in the 
Installer mode (from n.1 to n.14). 
h)  To exit the installer mode, move the slider switch to the 
AUTO or MAN positions. 
Abbreviated Set-Up Description 
e.g. Cl = Clock Format 
Factory Setting or New Choice
Press TEMP 
 or 
 to change
e.g. 12 = AM/PM Format
24 = 24hr Format 
Installer Set-up Number
(Press 
+ or - to change)
e.g. 1 = Clock Format
Brief Description of the 
Parameter Function. 
Specific Applications 
  Setting 
What do you need to change? 
 
Cycle/ 
Hour 
Minimum 
ON time 
(in minutes)
 
Note : All parameters listed below belong to category 2 – System 
Parameters (see Installer Parameters Table
Heating Gas 
Boilers 
(<30KW) 
No changes required 
 
Oil Boiler 
1.  Set Minimum ON Time to 4 minutes.  
2.  Set Cycle/Hour to 3. 
 
Thermal Actuator 
12 
Set Cycle/Hour to 12.  
 
Zone valve 
No changes required. 
Air 
conditioning 
 
 
 
1.  Configure the thermostat to allow switching between heating 
and cooling modes (set parameter n.4:HC to 1) 
2.  Set the thermostat accordingly to the required mode of 
operation (heating or cooling) by pressing the TEMP 
 or 
 
buttons together for 5 seconds.
 Modify the cooling program 
as required. 
 
Heat Pump/ 
Air conditioner 
1.  Set Minimum ON Time to 4 minutes. 
2.  Set Cycle/Hour to 3. 
 
Fan coil 
No changes required.