Trane Gas Unit Heaters Wartungshandbuch

Seite von 43
10
GKND-SVX01B-EN
Unit Dimensions and Weights
Table 1.
Performance and specification data: Separated Combustion Blower Unit Heater
Unit Size
100
125
150
175
200
225
250
300
350
400
PERFORMANCE DATA
(a)
Input
BTU/Hr
100,000
125,000
150,000
175,000
200,000
225,000
250,000
300,000
350,000
400,000
 (kW)
(29.3)
(36.6)
(43.9)
(51.2)
(58.6)
(65.9)
(73.2)
(87.8)
(102.5)
(117.1)
Output
BTU/Hr
80,000
100,000
120,000
140,000
160,000
180,000
200,000
240,000
280,000
320,000
  
(kW)
(23.4)
(29.3)
(35.1)
(41.0)
(46.9)
(52.7)
(58.6)
(70.3)
(82.0)
(93.7)
Thermal  Efficiency
%
80
80
80
80
80
80
80
80
80
80
Free Air Delivery CFM
cfm
1,200
1,575
1,975
2,300
2,400
2,600
2,850
3,950
4,600
4,800
 (m
3
/s)
(0.566)
(0.743)
(0.932)
(1.086)
(1.133)
(1.227)
(1.345)
(1.864)
(2.171)
(2.266)
Air Temperature Rise
°F
62
59
56
56
62
64
65
56
56
62
 (°C)
(34)
(33)
(31)
(31)
(34)
(36)
(36)
(31)
(31)
(34)
Outlet Velocity
fpm
880
950
1030
1045
965
935
930
1080
1090
1000
 (m/s)
(4.47)
(4.83)
(5.23)
(5.31)
(4.90)
(4.75)
(4.72)
(5.49)
(5.54)
(5.08)
Full Load Amps at 115V
8.3
9.8
10.6
10.6
15.2
15.2
15.2
15.2
18.6
18.6
MOTOR DATA
Motor
hp
1/4
1/3
1/2
1/2
3/4
3/4
3/4
3/4
1
1
(kW)
(0.19)
(0.25)
(0.37)
(0.37)
(0.56)
(0.56)
(0.56)
(0.56)
(0.75)
(0.75)
Type
SPH
SPH
SPH
SPH
SPH
SPH
SPH
SPH
cap.start cap.start
RPM
1725
1725
1725
1725
1725
1725
1725
1725
1725
1725
Amps @ 115V
5.1
6.6
7.4
7.4
12.0
12.0
12.0
12.0
15.4
15.4
DIMENSIONAL DATA
“A” Height to Top of Unit 
in.
31-1/4
31-1/4
36-1/4
36-1/4
36-1/4
36-1/4
36-1/4
36-1/4
36-1/4
36-1/4
(mm)
(794)
(794)
(921)
(921)
(921)
(921)
(921)
(921)
(921)
(921)
“B” Height to Top of Hanger
in.
34-1/16
34-1/16
39-1/16
39-1/16
39-1/16
39-1/16
39-1/16
39-1/16
39-1/16
39-1/16
(mm)
(865)
(865)
(992)
(992)
(992)
(992)
(992)
(992)
(992)
(992)
“C” Hanging Distance Width
in.
14-3/4
17-1/2
17-1/2
20-1/4
23
25-3/4
28-1/2
34
39-1/2
45
(mm)
(375)
(444)
(444)
(514)
(584)
(654)
(724)
(864)
(1003)
(1143)
“D” Discharge Opening Width
in.
15-3/8
18-1/8
18-1/8
20-7/8
23-5/8
26-3/8
29-1/8
34-5/8
40-1/8
45-5/8
(mm)
(391)
(460)
(460)
(530)
(600)
(670)
(740)
(879)
(1019)
(1159)
“E” Width of Unit
in.
17-7/8
20-5/8
20-5/8
23-3/8
26-1/8
28-7/8
31-5/8
37-1/8
42-5/8
48-1/8
(mm)
(454)
(524)
(524)
(594)
(664)
(733)
(803)
(943)
(1083)
(1222)
“F” to Centerline of Flue
in.
5-7/8
7-1/4
7-1/4
8-5/8
10
11-1/4
12-3/4
15-1/2
18-1/4
21
 (mm)
(149)
(184)
(184)
(219)
(254)
(286)
(324)
(394)
(464)
(533)
“G”  Hanging  Distance  Depth 
in.
18-1/2
18-1/2
18-1/2
20
20
23
23
23
23
23
(mm)
(470)
(470)
(470)
(508)
(508)
(584)
(584)
(584)
(584)
(584)
“H” Depth to Rear of Housing 
in.
42-3/4
44-3/8
44-3/8
47-3/16
47-3/16
50-7/8
48
50-7/8
50-7/8
51
(mm)
(1086)
(1127)
(1127)
(1199)
(1199)
(1292)
(1219)
(1292)
(1292)
(1295)
Flue  Size  Dia.
in.**
4
4
4
4
5
5
5
6
6
6
(mm)
(102)
(102)
(102)
(102)
(127)
(127)
(127)
(152)
(152)
(152)
Air  Inlet  Size
in.
4
4
4
4
5
5
5
6
6
6
(mm)
(102)
(102)
(102)
(102)
(127)
(127)
(127)
(152)
(152)
(152)
Blower Size
in.
9
10
10
12
12
12
12
(2) 10
(2) 12
(2) 12
Gas Inlet-Natural Gas
in.
1/2
1/2
1/2
1/2
1/2
3/4
3/4
3/4
3/4
3/4
Gas Inlet-LP Gas
in.
1/2
1/2
1/2
1/2
1/2
1/2 or 3/4
Approx. Shipping Wt.
lb
298
330
362
394
426
458
490
558
618
678
(kg)
(135)
(150)
(164)
(179)
(193)
(208)
(222)
(253)
(280)
(308)
Notes:
 1. For installations in Canada, any references to deration at altitudes in excess of 2000 ft. (610 m) are to be ignored. At altitudes of 2000 to 4500 ft. 
(610 to 1372 m), the unit must be derated to 90% of the normal altitude rating, and be so marked in accordance with the ETL certification.
 2. Legend: SPH = SPLIT PHASE, CAP. START = CAPACITOR START
(a) Ratings shown are for unit installations at elevations between 0 and 2000 ft. (610 m). For unit installations in USA above 2000 ft. (610 m), the unit 
input must be derated 4% for each 1000 ft. (305 m) above sea level; refer to local codes, or in absence of local codes, refer to the latest edition of the 
National Gas Code, ANSI Standard Z223.1 (N.F.P.A. No. 54).
** Refer to corresponding ** in 
.