Trane Gas Unit Heaters Wartungshandbuch

Seite von 53
12
GTND-SVX01B-EN
Unit Dimensions and Weights
Table 1.
Unit sizes 30–120: Performance and specification data
Unit Size
30
45
60
75
90
105
120
PERFORMANCE DATA
(a)
Input
Btu/h
30,000
45,000
60,000
75,000
90,000
105,000
120,000
 (kW)
(8.8)
(13.2)
(17.6)
(22.0)
(26.4)
(30.8)
(35.2)
Output
Btu/h
24,900
37,350
49,800
61,500
73,800
86,100
98,400
  
(kW)
(7.2)
(10.9)
(14.5)
(18.0)
(21.6)
(25.2)
(28.8)
Thermal  Efficiency
%
83
83
83
82
82
82
82
Free Air Delivery CFM
cfm
370
550
740
920
1,100
1,300
1,475
 (m
3
/s)
(0.175)
(0.260)
(0.349)
(0.434)
(0.519)
(0.614)
(0.696)
Air Temperature Rise
°F
60
60
60
60
60
60
60
 (°C)
(15)
(15)
(15)
(15)
(15)
(15)
(15)
Full Load Amps at 115V
3.0
3.0
4.1
4.1
6.4
6.4
6.4
Maximum Circuit Ampacity
3.5
3.5
4.8
4.8
7.5
7.5
7.5
MOTOR DATA:
Motor
hp
 1/20
 1/20
 1/12
 1/12
 1/10
 1/10
 1/10
(kW)
(0.04)
(0.04)
(0.06)
(0.06)
(0.075)
(0.075)
(0.075)
Type
SP
SP
SP
SP
SP
SP
SP
RPM
1650
1650
1050
1050
1050
1050
1050
Amps @ 115V
1.9
1.9
2.6
2.6
4.2
4.2
4.2
DIMENSIONAL DATA
“A” Jacket Height
in.
12-3/8
12-3/8
15-7/8
15-7/8
22-5/8
22-5/8
22-5/8
(mm)
(314)
(314)
(403)
(403)
(574)
(574)
(574)
“B” Overall Height
in.
13-1/4
13-1/4
16-13/16
16-13/16
23-9/16
23-9/16
23-9/16
(mm)
(337)
(337)
(427)
(427)
(598)
(598)
(598)
“C” Overall Depth
in.
25-7/8
25-7/8
26-3/16
26-3/16
26-3/8
26-3/8
26-3/8
(mm)
(632)
(632)
(665)
(665)
(670)
(670)
(670)
“D1” Center Line Height of Flue
(b)
in.
8-1/2
8-1/2
10-3/8
10-3/8
13-5/8
13-5/8
13-5/8
(mm)
(216)
(216)
(263)
(263)
(346)
(346)
(346)
“D2” Center Line Height of Air Intake
in.
8-1/2
8-1/2
8
8
8-5/8
8-5/8
8-5/8
(mm)
(216)
(216)
(203)
(203)
(219)
(219)
(219)
“E”  Fan  Diameter
in.
10
10
14
14
16
16
16
(mm)
(254)
(254)
(356)
(356)
(406)
(406)
(406)
“F” Discharge Opening Height
in.
10-13/16
10-13/16
14-7/16
14-7/16
21-3/16
21-3/16
21-3/16
(mm)
(275)
(275)
(367)
(367)
(538)
(538)
(538)
“G” Vent Connection Diameter
in.
4
4
4
4
4
4
(mm)
(102)
(102)
(102)
(102)
(102)
(102)
(102)
“H1” Center Line of Flue Connection From Side
in.
7-1/4
7-1/4
7-1/4
7-1/4
7-3/4
7-3/4
7-3/4
(mm)
(184)
(184)
(184)
(184)
(197)
(197)
(197)
“H2” Center Line of Air Intake From Side
in.
2-3/4
2-3/4
2-3/4
2-3/4
3-1/2
3-1/2
3-1/2
(mm)
(70)
(70)
(70)
(70)
(89)
(89)
(89)
Vent Size Requirements - Standard Combustion
 Category I Horizontal
(c)
in.
4
4
4
5
5
5
5
(mm)
(102)
(102)
(102)
(127)
(127)
(127)
(127)
 
Category  III  Horizontal
in.
4
4
4
4
4
4
4
(mm)
(102)
(102)
(102)
(102)
(102)
(102)
(102)
 
Category  I  &  III  Vertical
in.
4
4
4
4
4
4
4
(mm)
(102)
(102)
(102)
(102)
(102)
(102)
(102)
Vent Size Requirements - Separated Combustion
Exhaust  Diameter**
in.
4
4
4
4
5
5
5
(mm)
(102)
(102)
(102)
(102)
(127)
(127)
(127)
Intake  Air  Diameter
in.
4
4
4
4
5
5
5
(mm)
(102)
(102)
(102)
(102)
(127)
(127)
(127)
Unit Weight
lb
60
65
80
85
95
105
110
(kg)
(27)
(29)
(36)
(39)
(43)
(48)
(50)
Shipping Weight
lb
70
75
90
95
110
115
120
(kg)
(32)
(34)
(41)
(43)
(50)
(52)
(54)
(a) Ratings shown are for unit installations at elevations between 0 and 2000 ft. (610 m). For unit installations in USA above 2000 ft. (610 m), the unit 
input must be derated 4% for each 1000 ft. (305 m) above sea level; refer to local codes, or in absence of local codes, refer to the latest edition of the 
National Gas Code, ANSI Standard Z223.1 (N.F.P.A. No. 54). Also refer to 
. 
For installations in Canada, any reference to deration at altitudes in excess of 2000 ft. (610 m) are to be ignored. At altitudes of 2000 to 4500 ft. (610 
to 1372 m), the unit must be derated to 90% of the normal altitude rating, and be so marked in accordance with the ETL certification.
(b) For all installations, the flue collar is included with the unit and should be field-installed per the instructions included with the unit.
(c) 4”–5” reducer supplied where required.