Trane Gas Unit Heaters Wartungshandbuch

Seite von 53
Installation: Mechanical
GTND-SVX01B-EN
17 
Air for Combustion. 
The unit heater shall be installed in 
a location in which the facilities for ventilation permit 
satisfactory combustion of gas, proper venting, and the 
maintenance of ambient temperature at safe limits under 
normal conditions of use. The unit heater shall be located 
in such a manner as not to interfere with proper circulation 
of air within the confined space. When buildings are so 
tight that normal infiltration does not meet air 
requirements, outside air shall be introduced per Sections 
1.3.4.2 and 1.3.4.3 of ANSI Z223.1 for combustion 
requirements. A permanent opening or openings having a 
total free area of not less than one square inch per 
5,000 Btu/h (1.5 Kw) of total input rating of all appliances 
within the space shall be provided.
Note: Unit heater sizing should be based on heat loss 
calculations where the unit heater output equals or 
exceeds heat loss.
Clearances
Each gas unit heater shall be located with respect to 
building construction and other equipment so as to permit 
access to the Unit Heater. 
Unit sizes 30–120: Clearance between vertical walls and 
the vertical sides of the unit heater shall be no less than 
1  inch (25.4  mm). However, to ensure access to the control 
box and fan, a minimum of 18  inches (457  mm) is required 
for the fan, and control box side. A minimum clearance of 
1 inch (25.4 mm) must be maintained between the top of 
the Unit Heater and the ceiling. The bottom of the Unit 
Heater must be no less than 1 inch (25.4 mm) from any 
combustible. The distance between the flue collector and 
any combustible must be no less than 1 inch (25.4 mm).
Unit sizes 150–400: Clearance between vertical walls and 
the vertical sides of the unit heater shall be no less than 
6 inches (152 mm). However, to ensure access to the 
control box, a minimum of 18 inches (457 mm) is required 
for the control box side. A minimum clearance of 6 inches 
(152 mm) must be maintained between the top of the unit 
heater and the ceiling. The bottom of the unit heater must 
be no less than 12  inches (305  mm) from any combustible. 
The distance between rear of unit and vertical wall should 
be no less than 18 inches to maintain inlet air flow. The 
distance between the flue collector and any combustible 
must be no less than 6 inches (152 mm).
Also refer to 
 sections.
Note: Increasing the clearance distances may be 
necessary if there is a possibility of distortion or 
discoloration of adjacent materials.
Unit Mounting. 
WARNING
Overheating or Flooding Could Cause Fire 
or Explosion!
Overheating or flooding (where any part of the unit 
heater has been under water) could result in fire or 
explosion. Should overheating occur, or the gas supply 
fails to shut off, shut off the manual gas valve to the 
unit heater before shutting off the electrical supply. Do 
not use the unit heater if any part has been under 
water. Immediately call a qualified service technician to 
inspect the unit heater and replace any gas control 
which has been underwater. Failure to follow these 
recommendations could result in death or serious 
injury.
WARNING
Hazardous Gases and Flammable Vapors!
Exposure to hazardous gases from fuel substances 
have been shown to cause cancer, birth defects or other 
reproductive harm. Improper installation, adjustment, 
alteration, service or use of this product could cause 
flammable mixtures. To avoid hazardous gases and 
flammable vapors follow proper installation and set up 
of this product and all warnings as provided in this 
manual. Failure to follow all instructions could result in 
death or serious injury.
WARNING
Heavy Objects!
Make certain that the lifting methods used to lift the 
heater and the method of suspension used in the field 
installation of the heater are capable of uniformly 
supporting the weight of the heater at all times. Make 
certain that the structure to which the heater is 
mounted is capable of supporting its weight. Under no 
circumstances must the gas lines, the venting system 
or the electrical conduit be used to support the heater; 
or should any other objects (i.e. ladder, person) lean 
against the heater, gas lines, venting system or the 
electrical conduit for support. Failure to follow 
recommendations could result in death or serious 
injury.
NOTICE: 
Equipment Damage!
Unit heaters must be hung level from side to side and 
from front to back: 
Unit sizes 30–120: Refer to 
 through 
.
Unit sizes 150–400: Refer to 
 through 
Failure to do so will result in poor performance and or 
premature failure of the unit.