Gas Pipe Sizing
Pipe Sizing
To provide adequate gas pressure to the gas unit heater, 
size the gas piping as follows:
1.
Find the ft
3
/h by using the following formula:
2. Refer to 
. Match “Length of Pipe in Feet” 
with appropriate “Gas Input - ft
3
/h” value. This value 
can then be matched to the pipe size at the top of the 
column.
Example:
It is determined that a 67-foot (20.4-m) run of gas pipe 
is required to connect a 200 MBtu gas unit heater to a 
1,000 Btu/ft
3
 (0.29 kW) natural gas supply.
Using 
, a 1-inch pipe is needed.
Note: Refer to 
English/Metric unit conversion factors.
Important:
If more than one unit heater is to be served by the same 
piping arrangement, the total ft
3
/h input and length of 
pipe must be considered.
If the gas unit heater is to be fired with LP gas, consult 
your local LP gas dealer for pipe size information.
Heater installation for use with propane (bottled) gas 
must be made by a qualified LP gas dealer or installer. 
He/She will ensure that proper joint compounds are 
used for making pipe connections, that air is purged 
from lines, that a thorough test is made for leaks before 
operating the heater, and that it is properly connected 
to the propane gas supply system.
Before any connection is made to the existing line 
supplying other gas appliances, contact the local gas 
company to make sure that the existing line is of adequate 
size to handle the combined load.
WARNING
Fire Hazard!
Do not connect gas piping to this unit until a supply 
line pressure/leak test has been completed. Connecting 
the unit before completing the pressure/leak test may 
damage the unit gas valve and result in a fire hazard, 
which could result in death, serious injury, and property 
damage.
NOTICE: 
Equipment Damage!
Do not rely on a shut-off valve to isolate the unit while 
conducting gas pressure/leak tests. These valves may 
not be completely shut off, exposing the gas valve to 
excessive pressure and damage.
ft
3
/h
=
Input BTU/h/1000
1,000
200,000 BTU/h
=
200 ft
3
/h
1,000 BTU/ft
3