Motor Setup 
 205 
Optimizing Magnetization Current Ixx77, Slip Gain Ixx78  
 
Magnetization current 
 
 
Caution 
During  the  optimization  procedure,  the  motor  will  rotate  up  to  its 
maximum 
velocity. 
Make 
sure 
that 
the 
motor 
is 
well 
mounted/clamped and uncoupled from any rotating inertia.   
  
Always be ready to issue a Kill if the motor exceeds its maximum 
specified speed. 
 
With AC Induction motors, the magnetization current Ixx77 is used to provide a stator current component 
parallel to the estimated rotor magnetic field (the “direct” current -- the control loop then determines the 
magnitude of the “quadrature” current perpendicular to this component). 
 
In open loop mode, and given a fixed magnetization current Ixx77, the induction motor will accelerate at 
the slip gain rate Ixx78 and reach a certain base speed. This, theoretically, is the motor name plate speed. 
It usually specifies the maximum motor speed before applying field weakening.  
Field weakening consists of lowering the magnetization current in order to achieve speeds superior to the 
motor base speed (name plate). The  lower the  magnetization current, the  higher is the speed that can be 
achieved.    
 
Mag Current
Ixx77
Voltage/ 
Speed
(RPM)
Base 
Speed
Nominal Field 
Weakening
Nominal, at full motor voltage (230V)
208 VAC bus, Higher Ixx77
208 VAC bus, Optimized Ixx77
208 VAC bus, Lower Ixx77
Max Speed(s)
Before Field 
weakening