Trane Gas Unit Heaters Katalog
30
UH-PRC002-EN
Controls
Pilot Control
High efficiency units (centrifugal, propeller and duct furnaces) ship as standard with intermittent
pilot ignition. The separated combustion propeller and centrifugal fan unit heaters also ship as
standard with intermittent pilot ignition.
pilot ignition. The separated combustion propeller and centrifugal fan unit heaters also ship as
standard with intermittent pilot ignition.
Intermittent pilot ignition contains a solid-state ignition control system that ignites the pilot by
spark for each cycle of operation. When the pilot flame is proven, the main burner valve opens to
allow gas flow to the burners. Both the pilot and burners are extinguished during the off cycle.
spark for each cycle of operation. When the pilot flame is proven, the main burner valve opens to
allow gas flow to the burners. Both the pilot and burners are extinguished during the off cycle.
Intermittent pilot ignition is ideal for limited access installations where manual lighting of the pilot
may be difficult. Nuisance pilot outages on units mounted in areas subject to occasional severe
drafts can also be eliminated. Energy savings will be realized using this system as the pilot is
extinguished during the off cycle. Intermittent pilot ignition should be considered on units that
have long shutoff periods.
may be difficult. Nuisance pilot outages on units mounted in areas subject to occasional severe
drafts can also be eliminated. Energy savings will be realized using this system as the pilot is
extinguished during the off cycle. Intermittent pilot ignition should be considered on units that
have long shutoff periods.
Fan Control
The supply fan motor is activated directly through the fan time delay relay on indoor units provided
with single-phase motors up to one hp. Contactors or starters are required on all other units with
single-phase motors, 1-1/2 hp and above, and with all three-phase motors. On indoor units,
contactors and starters, where required, are provided (see
with single-phase motors up to one hp. Contactors or starters are required on all other units with
single-phase motors, 1-1/2 hp and above, and with all three-phase motors. On indoor units,
contactors and starters, where required, are provided (see
.)
Gas Controls
Single-Stage Control
Indoor gas heating units are provided with an automatic single-stage gas valve as standard. This
valve is an on/off type control, typically activated by a low voltage single-stage thermostat.
valve is an on/off type control, typically activated by a low voltage single-stage thermostat.
Two-Stage Control
Indoor units with optional two-stage control are provided with a two-stage gas valve capable of
firing at 100 percent and 50 percent of rated input. Ignition is at low fire (50 percent of the unit’s rated
input) and the unit is typically controlled by a low voltage two-stage thermostat.
firing at 100 percent and 50 percent of rated input. Ignition is at low fire (50 percent of the unit’s rated
input) and the unit is typically controlled by a low voltage two-stage thermostat.
Electronic Modulating Control
This optional control is available for use with natural gas units only. Units with electronic
modulating control are provided with an electronic modulating valve capable of firing from 100
percent to 50 percent of rated input. Ignition is at full fire (100 percent of unit’s rated input). The
electronic modulating valve is controlled by a room thermostat or a duct thermostat with remote
setpoint adjustment which modulates the gas input from 100 percent to 50 percent of rated input.
An optional override room thermostat is available for use with the duct thermostat. The override
room thermostat allows full fire and overrides the duct thermostat when the room temperature
falls below the override room thermostat’s setpoint.
modulating control are provided with an electronic modulating valve capable of firing from 100
percent to 50 percent of rated input. Ignition is at full fire (100 percent of unit’s rated input). The
electronic modulating valve is controlled by a room thermostat or a duct thermostat with remote
setpoint adjustment which modulates the gas input from 100 percent to 50 percent of rated input.
An optional override room thermostat is available for use with the duct thermostat. The override
room thermostat allows full fire and overrides the duct thermostat when the room temperature
falls below the override room thermostat’s setpoint.
Note: N/A on 30–75 MBh units.
Table 17. Contactors provided on indoor units
hp
Voltage
1/2
3/4
1
1-1/2
2
3
5
7-1/2
10
115/60/1
1
1
1
2
2
N/A
N/A
N/A
N/A
230/60/1
1
1
1
2
2
N/A
N/A
N/A
N/A
208/60/3
2
2
2
2
2
2
2
4
4
230/60/3
2
2
2
2
2
2
2
4
4
460/60/3
3
3
3
3
3
3
3
5
5
Notes:
1. Contactors not required or provided on units with single phase motors up to one hp.
2. Provided with contactor with line voltage holding coil on all 1-1/2 hp and above single-phase motors and on all 208/230V
three-phase motors up to five hp.
3. Provided with contactor with low (24V) holding coil on all 460 V three-phase motors up to five hp.
4. Provided with size 2 starter on all units with 7-1/2 and 10 hp 208/230V three-phase motors.
5. Provided with size 1 starter on all units with 7-1/2 and 10 hp 460V three-phase motors.