Trane Gas Unit Heaters Wartungshandbuch

Seite von 43
Installation: Mechanical
GLND-SVX01B-EN
13 
Access panels large enough to observe smoke and 
reflected light, and to detect the presence of leaks in the 
heating equipment, are required both upstream and 
downstream from gas duct furnaces. These panels must 
be sealed to prevent air leaks. If allowed by local 
regulations, install canvas connectors between the 
ductwork and fan discharge opening to eliminate the 
transmission of mechanical vibration.
Air Flow
The installation is to be adjusted to obtain an air 
throughput within the range specified on the appliance 
rating plate.
Combustion Inlet Air Ventilation
Inlet Air From Another Room
If the duct furnace is installed in a tightly constructed room 
or compartment, provide two inlet air openings. The size 
of each vent opening should be no less than one square 
inch (6.452 square centimeters) of free area for each 1000 
Btu/hr. (293 W) input. Each opening must not be less than 
100 square inches (645 square centimeters).
Inlet Air From Outdoors
If the enclosed space is to have inlet combustion air from 
the outside, the vent opening must not be smaller than one 
square inch (6.452 square centimeters) of free area for 
each 2500–3000 Btu/hr (733–879 W) input. Each opening 
must not be less than 100 square inches (645 square 
centimeters).
Bypass
When a gas duct furnace is installed to operate in 
conjunction with a summer air conditioning system, the 
cfm air delivery of the system blower should be adjusted 
to meet the design air volume requirements for cooling. If 
this cfm delivery is greater than that required for heating, 
resulting in a low air temperature rise, install a damper 
bypass around the gas duct furnace to bypass a portion of 
the air.
Suspension
Figure 8.
Recommended ductwork design for elbowed 
arrangement
WARNING
Heavy Objects!
Ensure that all hardware used in the suspension of each 
duct furnace is capable of supporting the unit weight. 
Failure to do so could result in unit falling off its 
mounting location, which could result in death or 
serious injury.
NOTICE: 
Equipment Damage!
The duct furnace must be hung level from side to side 
and front to back, from four suspension points provided 
at the top of the unit. Failure to do so could result in 
poor performance and/or premature failure of the unit. 
Refer to 
 
for typical suspension 
arrangements.
WARNING
Heavy Objects!
Make certain that the lifting methods used to lift the 
duct furnace and the method of suspension used in the 
field installation of the duct furnace are capable of 
uniformly supporting the weight of the furnace at all 
times. Make certain that the structure to which the 
furnace is mounted is capable of supporting its weight. 
Under no circumstances must the heater gas lines, the 
venting system or the electrical conduit be used for 
support. Failure to follow recommendations could 
result in death, serious injury, or property damage.