Trane Gas Unit Heaters Wartungshandbuch

Seite von 43
GLND-SVX01B-EN
27 
Start-Up
Operation
Power Vented Duct Furnaces with 
Intermittent (Spark) Pilot Ignition
Explanation of Controls
1.
The duct furnace is equipped with a dual automatic gas 
valve and electric ignition device (separate from the 
gas valve on most models) which provide the following 
functions:
a. The duct furnace is equipped with a power vent 
system consisting of a power venter motor and 
blower, pressure switch, and sealed flue collector in 
place of the conventional draft diverter.
b. The power venter motor is energized by the room 
thermostat on a call for heat. The pressure switch 
measures the flow through the vent system and 
energizes the indirect spark ignition system when 
the flow is correct.
c. The indirect spark ignition system consists of an 
ignition control module, a dual combination gas 
valve, and a spark-ignited pilot burner. When the 
pressure switch closes, the pilot valve opens and a 
spark is generated to light the pilot burner. When 
the flame sensing circuit senses that pilot flame is 
established, the main gas valve is opened to supply 
gas to the main burners. When the thermostat is 
satisfied, the vent system is de-energized and both 
valves are closed to stop all flow of gas to the unit.
d. Pilot solenoid valve also functions as a main gas 
valve to provide redundancy.
e. Pressure regulator provides proper and steady gas 
pressure to the main burners.
f. Manual shutoff valve for service and long term 
shut-down. (Separate from the automatic valve on 
some models.)
2. The high limit switch interrupts the flow of electric 
current to the main gas valve in case the heater 
becomes overheated.
3. The fan switch delays the operation of the fan until the 
heater is warmed, then keeps the fan running after the 
gas has been turned off until the useful heat has been 
removed. The start-up fan delay must not exceed 
90 seconds from a cold start.
4. The wall thermostat (supplied optionally) is a 
temperature sensitive switch which operates the vent 
system and ignition system; it turns the main gas valve 
ON or OFF to control the temperature of the space 
being heated. It must be mounted on a vibration free, 
vertical surface away from air currents, in accordance 
with the instructions furnished with the thermostat 
(also refer to 
Start-Up
1.
Open the manual valve supplying gas to the unit 
heater, and with the union connection loose, purge air 
from the gas line. Tighten the union and check for gas 
leaks, using a soapy water solution only.
2. Open the manual valve on the unit heater.
3. Turn ON electrical power.
WARNING
Check and Test Safety Devices!
It is the installer’s responsibility to check all safety 
controls! Check and test the operational functions of all 
safety devices supplied with this unit, and ensure that 
all are operating effectively. Failure to do so could result 
in unsafe conditions and could result in death, serious 
injury or property damage.
NOTICE: 
Operate Unit within Specified Units!
Never operate the unit beyond the specified limits, 
severe damage to, and/or premature failure of the unit 
will result!
WARNING
Risk of Fire and Carbon Monoxide 
Poisoning!
The pressure switch MUST NOT be bypassed. The unit 
MUST NOT be fired unless the power venter is 
operating. Failure to follow these recommendations 
could result in death or serious injury.
NOTICE: 
Additional Devices!
The addition of external draft hoods or power venters is 
not permitted. Addition of such devices could cause 
severe unit malfunction or failure!
WARNING
Hazard of Explosion!
Never use an open flame to detect gas leaks. Explosive 
conditions may occur. Use a leak test solution or other 
approved methods for leak testing. Before attempting 
to light or relight the pilot, wait 5 minutes to allow gas 
which may have accumulated in the burner 
compartment to escape. Failure to follow 
recommended safe leak test procedures or pilot 
lighting/relighting instructions could result in death or 
serious injury or equipment or property-only-damage.