Trane Gas Unit Heaters Wartungshandbuch

Seite von 35
11
GBNE-SVX001A-EN
Figure 4 - Pipe Installation, Standard Controls
The appliance and its individual shutoff valve must be 
disconnected from the gas supply piping system during any 
pressure testing of that system in excess of 1/2 psig (3.5 kPa).
The appliance must be isolated from the gas supply 
piping system by closing its individual manual shutoff 
valve during any pressure testing of the gas supply 
piping system at test pressures equal to or less than  
1/2 psig (3.5 kPa).
Table 4 - Gas Piping Requirements
SINGLE STAGE GAS PIPING REQUIREMENTS*
GasType  
 
Natural Gas  
Propane (LP) Gas
Manifold 
 
3.5 inch WC 
10.0 inch WC 
Pressure 
 
(0.9 kPa) 
(2.5 kPa)
 
 
14.0 inch WC Max. 
14.0 inch WC Max.
Supply Inlet   
(3.5 kPa) 
(3.5 kPa)
Pressure 
 
5.0 inch WC Min. 
11.0 inch WC Min.
 
(1.2 kPa) 
(2.7 kPa)
*For single stage application only at normal altitudes.
   
1.  Install the gas piping in accordance with applicable local 
codes.
2.  Check gas supply pressure. Each unit heater must be 
connected to a manifold pressure and a gas supply 
capable of supplying its full rated capacity as specified 
in Table 4. A field LP tank regulator must be used to limit 
the supply pressure to a maximum of 14 inches W.C. (3.5 
kPa). All piping should be sized in accordance with the 
latest edition of ANSI Standard Z223.1 (NFPA 54), 
National Fuel Gas Code; in Canada, according to CSA 
B149. See Tables 1 & 3 for correct gas piping size. If gas 
pressure is excessive on natural gas applications, install 
a pressure regulating valve in the line upstream from the 
main shutoff valve.
3.  Adequately support the piping to prevent strain on the 
gas manifold and controls.
4.  To prevent the mixing of moisture with gas, run the take-
off piping from the top, or side, of the main.
5.  Standard Unit Heaters, optional two-stage units are 
supplied with a combination valve which includes:
 
a. Manual "A" valve
 
b. Manual "B" valve
 
c. Solenoid valve
 
d. Pressure regulator
 
Pipe directly into the combination valve (see Figure 4).
6.  Gas valve has a pressure test post requiring a  
3/32 inch hex head wrench to read gas supply and 
manifold pressures. Open 1/4 turn counterclockwise to 
read, turn clockwise to close and reseat. A 5/16 inch ID 
hose fits the pressure post.
7.  Provide a drip leg in the gas piping near the gas unit 
heater. A ground joint union and a manual gas shutoff 
valve should be installed ahead of the unit heater 
controls to permit servicing. The manual shutoff valve 
must be located external to the jacket (See  Figure 4).
8.  Make certain that all connections have been adequately 
doped and tightened.
NOTICE: Use pipe joint sealant resistant to the action of 
liquefied petroleum gases regardless of gas conducted.
Installation 
(continued)
Pipe Installation
CAUTION
Do not over tighten the inlet gas piping into the valve. This may 
cause stresses that will crack the valve!
WARNING
Check all pipe joints for leakage using a soap solution or other 
approved method.  Never use an open flame or severe personal 
injury or death may occur!
WARNING
Never use an open flame to detect gas leaks. Explosive condi-
tions may exist which may result in personal injury or death!
D3631C
D3631C