Trane Gas Unit Heaters Wartungshandbuch

Seite von 35
19
GBNE-SVX001A-EN
Venting
Observe the following precautions when venting the unit:
1.  Use flue pipe of the same size as the flue connections 
on the gas unit heater (See Table #1). All heaters should 
be vented with double wall or single wall vent, a factory 
built chimney, or a lined brick and mortar chimney that 
has been constructed in accordance with the National 
Building Code. Type B vent should only be used for 
vertical rise portions of a Category I vent pipe system. 
Type B vent pipe should not be used for horizontal runs 
of vent pipe.
2.  Provide as long a vertical run of flue pipe at the gas unit 
heater as possible. A minimum of 5' (1.5m) of vertical 
flue is required. The top of the vent pipe should extend at 
least 2' (0.61m) above the highest point on the roof. Install 
a weather cap over the vent opening. Consideration 
should be made for anticipated snow depth.
3.  Slope horizontal runs upward from the gas unit heater at 
least 1/4" per foot (21mm/m) minimum.  Horizontal runs 
should not exceed 75% of the vertical height of the vent 
pipe, or chimney, above the flue pipe connection, up to 
a maximum length of 10' (3m). Horizontal portions of the 
venting system shall be supported at minimum intervals 
of 4' (1.2m). In Canada, support at minimum intervals of 
3' (1m).
4.  Use as few elbows as possible.
5.  Seal all vent pipe joints and seams to prevent 
leakage. Use General Electric RTV-108, Dow 
Corning RTV-732, or equivalent silicone sealant  
with a temperature rating of 500 degrees F, or 3M #425 
aluminum foil tape (or equivalent).
6.  Avoid running vent pipe through unheated spaces.
7.  When this cannot be avoided, insulate the pipe to 
prevent condensation of moisture on the walls of the 
pipe.
8.  Do not damper the flue piping. Failure to open such a 
damper prior to operating the gas unit heater will result 
in the spillage of flue gas into the occupied space.
9.  Avoid installing units in areas under negative pressure 
due to large exhaust fans or air conditioning. When 
required, a flue vent fan should be installed in 
accordance with the instructions included with the fan.
10.  Vent connectors serving Category I and Category II 
heaters shall not be connected into any portion of 
mechanical draft systems operating under positive 
pressure.
ANSI now organizes vented 
appliances into four categories. 
Venting Categories
 
Non 
 
  
 
Condensing Condensing
 Negative
 
Vent 
    I  
II
 Pressure 
 
 Positive
 
Vent 
    III     IV
 Pressure 
 
Vertically Vented Unit Heaters (Category I)
Category I
Includes non-condensing appliances 
with negative vent pressure, like the 
traditional atmospheric unit heater.
Category II
Groups condensing appliances  
with negative vent pressure.
Category III
Appliances are non-condensing  
and operate with a positive vent 
pressure.
Category IV
Covers condensing appliances with 
positive vent pressure.
NOTICE: Category II and IV do not 
apply to equipment specified within 
this manual.
All unit heaters must be vented! All Venting installations shall be in accordance with the latest edition of Part 7, Venting of 
Equipment of the National Fuel Gas Code, ANSI Z223.1 (NFPA 54), or applicable provisions of local building codes. Refer to 
page 21 for Canadian installations. Refer to Figures 7, 8, 9A, 9B, 10A and 10B.
Do not damper or add heat recovery devices to the flue piping. Failure to open such a damper prior to operating  
gas unit will result in the spillage of flue gas into the occupied space.
WARNING
CARBON MONOXIDE! Your venting system must not be blocked by any snow, snow drifts, or any foreign matter. Inspect your venting 
system to ensure adequate ventilation exists at all times! Failure to heed these warnings could result in Carbon Monoxide Poisoning 
(symptoms include grogginess, lethargy, inappropriate tiredness, or flu-like symptoms).