Trane Gas Unit Heaters Wartungshandbuch

Seite von 41
Installation: Piping
GMND-SVX01B-EN
17 
Pipe Installation
1.
Install the gas piping in accordance with applicable 
local codes.
2. Check gas supply pressure. Each duct furnace must be 
connected to a gas supply capable of supplying its full 
rated capacity as specified in 
. A field LP 
tank regulator must be used to limit the supply 
pressure to maximum of 14 in. wc (3.5 kPa). All piping 
should be sized in accordance with the latest edition of 
ANSI Standard Z223.1 National Fuel Gas Code; in 
Canada, according to CGA-B149. See 
, and 
 for correct gas 
piping size.
If gas pressure is excessive on natural gas applications, 
install a pressure regulating valve in the line upstream 
from the main shutoff valve.
3. To prevent the mixing of moisture with gas, run the 
take-off piping from the top, or side, of the main.
4. Duct furnaces are shipped with a combination valve 
which includes:
a. Manual “A” valve
b. Manual “B” valve
c. Solenoid valve
d. Pilot safety
e. Pressure regulator
Table 4.
Gas pipe size
(a)
Nominal 
Iron Pipe 
Size, in.
Internal 
Diameter, 
in. (mm)
Length of Pipe, ft (m) 
10
20
30
40
50
60
70
80
90
100
125
150
175
200
(3.0) (6.1) (9.1) (12.2) (15.2) (18.3) (21.3) (24.4) (27.4) (30.5) (38.1) (45.7) (53.3) (61.0)
1/2
0.622
175
120
97
82
73
66
61
57
53
50
44
40
37
35
(16)
(4.96) (3.40) (2.75) (2.32) (2.07) (1.87) (1.73) (1.61) (1.50) (1.42) (1.25) (1.13) (1.05) (0.99)
3/4
0.824
360
250
200
170
151
138
125
118
110
103
93
84
77
72
(21)
(10.2) (7.08) (5.66) (4.81) (4.28) (3.91) (3.54) (3.34) (3.11) (2.92) (2.63) (2.38) (2.18) (2.04)
1
1.049
680
465
375
320
285
260
240
220
205
195
175
160
145
135
(27)
(19.3) (13.2) (10.6) (9.06) (8.07) (7.36) (6.80) (6.23) (5.80) (5.52) (4.96) (4.53) (4.11) (3.82)
1-1/4
1.380
1400
950
770
660
580
530
490
460
430
400
360
325
300
280
(35)
(39.6) (26.9) (21.8) (18.7) (16.4) (15.0) (13.9) (13.0) (12.2) (11.3) (10.2) (9.20) (8.50) (7.93)
1-1/2
1.610
2100
1460
1180
990
900
810
750
690
650
620
550
500
460
430
(41)
(59.5) (41.3) (33.4) (28.0) (25.5) (22.9) (21.2) (19.5) (18.4) (17.6) (15.6) (14.2) (13.0) (12.2)
2
2.067
3950
2750
2200
1900
1680
1520
1400
1300
1220
1150
1020
950
850
800
(53)
(112)
(77.9) (62.3) (53.8) (47.6) (43.0) (39.6) (36.8) (34.5) (32.6) (28.9) (26.9) (24.1) (22.7)
2-1/2
2.469
6300
4350
3520
3000
2650
2400
2250
2050
1950
1850
1650
1500
1370
1280
(63)
(178)
(123)
(99.7) (85.0) (75.0) (68.0) (63.7) (58.0) (55.2) (52.4) (46.7) (42.5) (38.8) (36.2)
3
3.068
11000 7700
6250
5300
4750
4300
3900
3700
3450
3250
2950
2650
2450
2280
(78)
(311)
(218)
(177)
(150)
(135)
(122)
(110)
(105)
(97.7) (92.0) (83.5) (75.0) (69.4) (64.6)
4
4.026
23000 15800 12800 10900 9700
8800
8100
7500
7200
6700
6000
5500
5000
4600
(102)
(651)
(447)
(362)
(309)
(275)
(249)
(229)
(212)
(204)
(190)
(170)
(156)
(142)
(130)
Notes:
 1. Determine the required ft
3
/h by dividing the rated heater input by 1000. For SI / Metric measurements: Convert unit Btu/h to kilowatts. Multiply the 
unit input (kW) by 0.0965 to determine m
3
/h.
 2. FOR NATURAL GAS: Select the pipe size directly from the table.
 3. FOR PROPANE GAS: Multiply the ft
3
/h (m
3
/h) value by 0.633; then use the table.
 4. Refer to the metric conversion factors listed in 
 for more SI unit measurements/conversions.
(a) Maximum capacity of pipe in cubic feet of gas per hour (cubic meters per hour) for gas pressures of 0.5 psig (3.5 kPa) or less, and a pressure drop of 
0.5 inch water column (124.4 Pa) (based on a 0.60 specific gravity gas).
WARNING
Hazard of Explosion!
Adequately support the piping to prevent strain on the 
gas manifold and controls. To prevent explosion, fire, or 
gas leaks, support piping so that piping does not sag or 
put pressure on the burners internal to the unit. Failure 
to follow these recommendations could result in death 
or serious injury or equipment or property-only-
damage.