Trane CAH-SVX01A-EN Benutzerhandbuch

Seite von 60
Routine Maintenance
54
 CAH-SVX01A-EN
See “
 WARNING Hazardous 
Voltage with Capacitors!” on 
page 49 regarding 
disconnection of power.
 WARNING
Hazardous Chemicals!
Coil cleaning agents can be either 
acidic or highly alkaline. Handle 
chemical carefully. Proper handling 
should include goggles or face 
shield, chemical resistant gloves, 
boots, apron or suit as required. For 
personal safety refer to the cleaning 
agent manufacturer’s Materials 
Safety Data Sheet and follow all 
recommended safe handling 
practices. Failure to follow all safety 
instructions could result in death or 
serious injury.
Internal Insulation
The process of cooling and 
dehumidification produces 
condensate that must be 
continuously removed from the air-
handling unit. The section of the unit 
from the entering air side of the 
cooling coil to the leaving edge of 
the drain pan is considered to be the 
“wet” section of the unit. Other 
potentially “wet” sections are 
immediately downstream of a 
humidifier and/or an outside air 
intake section.
Internal insulation in areas of the 
unit that are normally considered to 
be “dry” must also be periodically 
inspected to assure the insulation is 
clean and dry. Wet insulation in an 
area that is normally considered to 
be “dry” can indicate an operational 
problem (refer to the 
“Troubleshooting” section on 
page 56 for further information). The 
equipment should be inspected a 
minimum of every six months or 
more frequently as operating 
experience dictates. 
Accumulated dirt and other organic 
matter exposed to water or extended 
periods of high relative humidity 
(60 percent or higher) can support 
microbial growth, which must be 
removed to prevent the unit from 
becoming a contaminant source.
If evidence of contamination exists 
in either the wet or dry sections:
Determine and eliminate the 
cause.
Remove the contamination.
Sanitize the affected area.
See the “Troubleshooting” section 
on page 56 for assistance in 
identifying the cause.
If microbial growth on a non-porous 
insulating surface (closed cell 
insulation or sheet metal surface) is 
observed:
1
Disconnect all electrical power to 
the unit.
2
Wearing the appropriate 
personal protective equipment, 
use a brush for sheet metal 
surfaces or a soft sponge on a 
foil face or closed cell foam 
surface to mechanically remove 
the microbial growth.
Note: Be careful not to damage the 
non-porous surface of the insulation. 
3
Install a block-off to prevent 
spray from going into a dry 
section of the unit and/or system 
ductwork. 
4
Thoroughly clean all areas with 
an EPA-approved sanitizer 
specifically designed for HVAC 
use.
5
Rinse the affected surfaces 
thoroughly with fresh water and 
a fresh sponge to prevent 
potential corrosion of the drain 
pan and drain line.
6
Repeat steps 4 and 5 as 
necessary.
7
Confirm the drain line is open 
following the cleaning process.
8
Allow the unit to dry thoroughly 
before putting it back into 
service.
9
Replace all panels and parts and 
restore electrical power to the 
unit.
10 Be careful that any contaminated 
material does not contact other 
areas of the unit or building. 
Properly dispose of all 
contaminated materials and 
cleaning solution.
To clean a porous insulating surface 
(fiberglass insulation):
1
Disconnect all electrical power to 
the unit.
2
Wearing the appropriate 
personal protective equipment, 
use a vacuum device with a 
HEPA filter (99.97 percent 
efficient at 0.3 micron particles) 
to remove the accumulated dirt 
and organic matter. 
Note: Be careful not to tear the 
insulation surface or edges.
3
Confirm the drain line is open 
following the cleaning process.
4
Allow the unit to dry thoroughly 
before putting it back into 
service.
5
Replace all panels and parts and 
restore electrical power to the 
unit.
6
Be careful that any contaminated 
material does not contact other 
areas of the unit or building. 
Properly dispose of all 
contaminated materials and 
cleaning solution.