Trane OABE OADE OAKE OANE (Water Source Heat Pump) Katalog

Seite von 67
OAU-PRC003A-EN
17
Application Considerations
Establishing Capacity Requirements
Determining the OAU capacity requirements requires careful thought. Light Commercial 
equipment is typically selected based on design sensible conditions. Since latent loads drive the 
need for the OAU, base the selection on design latent conditions.
Cooling & Dehumidification Selection Criteria
Evaporator Design Entering Conditions
For many climates the peak outdoor air enthalpy occurs at a time when the outdoor dry-bulb 
temperature is not the highest. Refer to the chapter on climatic design information in the ASHRAE 
Handbook of Fundamentals. The cooling and dehumidification design condition data is provided 
three ways:
1.
Design dry-bulb temperature with mean coincident wet bulb temperature
2. Design wet-bulb temperature with mean coincident dry-bulb temperature
3. Design dew point temperature with mean coincident dry-bulb temperature
The design wet-bulb condition typically represents a significantly higher outdoor air enthalpy than 
the design dry-bulb condition. Use the condition that represents the highest enthalpy as the 
entering evaporator selection condition.
Evaporator Design Leaving Conditions
Due to the uncertainty of the local terminal unit’s latent capacity at part load, it is usually most 
straightforward to size the OAU to handle the entire latent load on the system, both indoor and 
outdoor. With this design approach, the terminal units may do some latent cooling 
(dehumidification) during periods of higher sensible load. At these times, the space will run slightly 
drier than the design RH limit. This is why it makes sense to select the OAU to limit the space RH 
to a maximum allowable level for those conditions when the terminal units are providing no space 
latent cooling, such as 60 percent RH. Using lower humidity limits may result in an unnecessary 
increase in system operating energy use.
, and 
 to identify the appropriate supply air dew point 
for specific design conditions. For a more detailed discussion on determining the selection criteria 
of a OAU, refer to SYS-APG001-EN (Application Guide: Designing Dedicated Outdoor-Air Systems
or SYS-APM004-EN (Applications Engineering Manual: Dehumidification in HVAC Systems). 
Figure 9.
Psychrometric chart with cooling and heating only
Dry Bulb Temperature
Dewpoint T
emperature
W
et Bulb T
emperature
t3
t4
heating
t1
t2
cooling