Trane OABE OADE OAKE OANE (Water Source Heat Pump) Katalog

Seite von 67
OAU-PRC003A-EN
19
Application Considerations
The Trane OAU utilizes recovered energy from the cooling process to reheat the air leaving the 
evaporator coil as required to meet the discharge air setpoint. The reheat refrigeration circuit is 
adequate to deliver enough reheat to supply neutral-temperature air (e.g., 75°F dry-bulb) under 
most operating conditions. On very low load days, the reheat circuit may not contain enough 
energy to meet the desired reheat setpoint.
Heating
The OAU has electric, heat pump, or gas heat options. The electric heat option is available in 0°F–
80°F temperature rise offerings with SCR modulation. This means that the lowest temperature rise 
provided depends only on heater size and unit airflow. Calculate the temperature rise to confirm 
that it provides acceptable control. The electric heat will modulate to maintain heating setpoint.
When using hot water heat, the unit controller will modulate a field-provided coil control valve. 
Provide an ethylene glycol and water mixture or other means of freeze protection for the hot water 
coil if the OAU will be subject to sub-freezing temperatures.
Capacity Control
The capacity control system on the Horizon™ Outdoor Air Unit is flexible enough to accommodate 
a variety of system applications. These applications include:
treating outdoor air to supply a single space or multiple spaces or 
simultaneously meet building make-up air needs while controlling the temperature and relative 
humidity of a single space. 
Each of these applications requires careful consideration to achieve the desired results. 
Discharge Air Control
For many multiple space, dedicated outdoor air systems, the OAU will continuously supply outdoor 
air at a dry-bulb setpoint and a dew point that does not exceed its dew point setpoint. This control 
approach is simple because it allows the OAU to function independent of local terminal unit 
operation or actual space conditions. If the unit selection criteria is determined using the method 
suggested in
, the Outdoor Air Unit will limit the space 
relative humidity to the target level. 
Table 3.
Supply air dew point temperature, 75°F at 50 percent RH space limit
Latent Load
 Btu/h per Person
cfm per person
10
15
20
25
30
35
40
45
50
55
60
100
48.4
50.8
51.9
52.6
53
53.3
53.6
53.8
53.9
54
54.1
120
46.8
49.8
51.3
52.1
52.6
53
53.3
53.5
53.6
53.8
53.9
140
45.2
48.9
50.6
51.5
52.2
52.6
52.9
53.2
53.4
53.5
53.7
160
47.9
49.8
51
51.7
52.2
52.6
52.9
53.1
53.3
53.5
180
46.8
49.1
50.4
51.3
51.8
52.3
52.6
52.9
53.1
53.3
200
45.7
48.4
49.8
50.8
51.5
51.9
52.3
52.6
52.8
53.0
220
47.6
49.3
50.3
51.1
51.6
52
52.3
52.6
52.8
240
46.8
48.7
49.8
50.7
51.3
51.7
52.1
52.4
52.6
260
46
48.1
49.4
50.3
50.9
51.4
51.8
52.1
52.4
280
45.2
47.4
48.9
49.8
50.6
51.1
51.5
51.9
52.2
300
46.8
48.4
49.4
50.2
50.8
51.3
51.6
51.9
320
46.2
47.9
49
49.8
50.5
51
51.4
51.7
340
45.5
47.3
48.6
49.5
50.2
50.7
51.1
51.5
360
46.8
48.2
49.1
49.8
50.4
50.9
51.3
380
46.3
47.7
48.7
49.5
50.1
50.6
51
400
45.7
47.3
48.4
49.2
49.8
50.4
50.8
420
45.2
46.8
48
48.9
49.6
50.1
50.6
440
46.3
47.6
48.5
49.3
49.8
50.3
460
45.9
47.2
48.2
49
49.6
50.1
480
45.4
46.8
47.9
48.7
49.3
49.8
500
46.4
47.5
48.4
49.1
49.6
Note:
Minimum dew point selectable is 45°F.