Emerson 3812 User Manual

Page of 138
92
Using AMS Device Manager to configure the meter
Section 4: Configuration
Daniel 3812 Liquid Ultrasonic Flow Meter Installation Manual
May 2015
3-9000-765 Rev H
h.
Click the 
Service Tools|Trends 
tab to display the device variables (uncorrected 
volume flow rate, pressure and temperature) trends.
Figure 4-18  AMS Device Manager - Service Tools Trends  
Primary and Secondary variables display real-time uncorrected volume flow rate 
trends. The third and fourth variables charts displays trends for temperature and 
pressure.
15.
Click the 
Service Tools|Routine Maintenance
 tab. Click 
Analog Output 1 Trim
 to perform a 
digital to analog trim adjustment of the first milliampere output. The 4mA and 20mA 
output current values should equal  the plant’s standard values. Click 
Yes
 to confirm the 
configuration changes.  Repeat this step to trim Analog Output 2 current. Click 
Apply
 to 
write the output trim values to the meter. Click 
OK
 to navigate back to the Service Tools 
page.
16.
Click the 
Service Tools|Zero Calibration
 tab. See 
 
 to configure the zero flow parameters.
17.
After you have changed and written the configuration changes to the meter do the 
following:
a.
Enable the Write Protect switch on the CPU Module to protect the meter’s 
configuration.
b.
Replace the end cap and if required, apply security seals through the endcap 
holes and through the hex head bolts that secure the Bracket/Cover to the Base 
enclosure. 
 
Note: The next time you connect to the device using Daniel MeterLink, the 
Monitor page displays a Meter status alarm that the configuration has changed 
and remains latched until acknowledged. Click 
Ack
 (acknowledge) to clear the 
alarm.