Daniel 3812 Liquid Ultrasonic Flow Meter Installation Manual
Section 3: Electrical installation
3-9000-765 Rev H
May 2015
CPU Module labeling and LED indicators
 53
Ethernet communications
The Ethernet port IP address, subnet mask, and gateway address are software-configurable. In 
addition, a meter can be configured to act as a DHCP (Dynamic Host Configuration Protocol) 
server to assign an IP address to a PC or laptop running Daniel MeterLink. The DHCP server 
facility is not intended to act as a general purpose DHCP server for a wider network. To this end, 
no user control is provided over the class or range of IP addresses the unit provides. A standard 
twisted pair (Cat-5) cable should be used for Ethernet wiring. 
It is strongly recommended that the meter be configured using an independent (off-network) 
single host. After configuration of the meter, the DHCP option must be turned off if used on a 
LAN/WAN.
Use ethernet cable (Daniel P/N 3-3400-079) to connect the PC to the meter. 
A DIN 41612 48-pin connector is the interface from the CPU Module to the Field Connection 
Board (male end located on the back of the Field Connection Board). 
Table 3-3  Ethernet cable to PC communication
Ethernet communication
Wire color
CPU
White w/Orange Stripe 
 TX+
Orange w/White Stripe
 TX -
White w/Green Stripe
RX+
Green w/White Stripe
RX -
RESTRICT ETHERNET AND SERIAL CONNECTIVITY USAGE
Failure to restrict Ethernet and communication access to the Daniel 3812 Liquid Ultrasonic 
Flow Meter can result in, among other things, unauthorized access, system corruption, and/
or data loss.
User is responsible for ensuring that physical access and Ethernet or electronic access to the 
Daniel 3812 Liquid Ultrasonic Flow Meter is appropriately controlled and any necessary 
security precautions, such as, establishing a firewall, setting password permissions and/or 
implementing security levels.
RX+
TX+
TX-
RX-