APC BE750G User Manual

Page of 8
Installation Guide 
Back-UPS
 BE750G Series
Specifications
Inventory
Safety
This UPS is intended for indoor use only. 
Do not operate this UPS in direct sunlight, in 
contact with fluids, or where there is 
excessive dust or humidity.
Be sure the air vents on the UPS are not 
blocked. Allow adequate space for proper 
ventilation.
The battery typically lasts for two to five years. Environmental factors impact 
battery life. Elevated ambient temperatures, poor quality utility power, and frequent 
short duration discharges will shorten battery life.
Connect the Back-UPS power cable directly to a wall outlet. Do not use surge 
protectors or extension cords.
Input
Voltage
120 Vac
 
Nominal
Frequency
50 Hz/60 Hz auto sensing
Brownout Transfers
92 Vrms Typical
Over-voltage Transfer
139 Vrms Typical
Output
UPS Capacity 
(5 battery backup outlets)
750 VA, 450 W
Total Amperage (all outlets)
12 A (including UPS output)
Voltage - On Battery
115 Vrms ± 8% step approximated sine wave
Frequency - On Battery
50 Hz/60 Hz ± 1 Hz
Transfer Time
6 ms Typical, 10 ms maximum
Protection and 
Filtering
AC Surge Protection
Full time, 354 Joules
Phone/DSL/FAX surge protection
Single line (2 wire)
Cable/CAT V/DSS surge protection
One coax input/output
Network surge protection
10/100 Base -T ethernet
EMI/RFI Filter
Full time
AC Input
Resettable circuit breaker
Battery
Type
Sealed, maintenance-free, lead acid
Replacement battery cartridge RBC17
Average Life
3 - 5 years depending on the number of discharge cycles and 
environmental temperature
Physical
Net Weight
11 lb (5 kg)
Dimensions 
Length x Width x Height
14 in x 7 in x 4 in
36 cm x 18 cm x 9 cm
Operating Temperature
32º F to 104º F (0º C to 40º C)
Storage Temperature
5º F to 113º F (–15º C to 45º C)
Operating Relative Humidity
0 to 95% non-condensing humidity
Operating Elevation
0 to 10,000 ft (0 to 3000 m)
EMC 
Compliance
This device complies with part 68 and part 15 of the FCC rules. Operation is subject to the following two 
conditions: (1) This device may not cause harmful interference, and (2) This device must accept any 
interference received, including interference that may cause undesired operation.
bu