Electrical Requirements
47
M414905
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
50 and 75 Pound Electric Models
Refer to Table 10
NOTE: Wire size and breaker ratings were 
obtained from the Canadian Electrical Code for 
75 C. wire and are intended for use as a guideline 
only. Electrical connections should be made by a 
qualified electrical contractor in accordance with 
all applicable local and national requirements.
NOTE: Electrical specifications below are subject 
to change without notice. Always refer to product 
serial plate for most current specifications of 
product being installed.
NOTE: Use copper conductors only.
NOTE: Connect to individual branch circuit.
NOTE: 3 Phase Only – Each tumbler must be 
connected to its own individual branch circuit 
breaker, not fuses, to avoid the possibility of “single 
phasing” and causing premature failure of the 
motor(s).
Serial Plate Rating
Terminal Block 
Connections 
Required
Serial Plate Amps
Recommended Circuit
Nonreversing
Reversing
Breaker 
Rating
Wire Size
AWG (mm
2
)
240V/50Hz/1ph
(50 Pound only)
L1, Neutral and Ground
93
95
125A – 1 pole
1 (42.4)
200-208V/60Hz/3ph
L1, L2, L3 and ground
89
88
125A – 3 pole
1 (42.4)
200V/50Hz/3ph
L1, L2, L3 and ground
84
85
125A – 3 pole
1 (42.4)
230V/50Hz/3ph
L1, L2, L3 and ground
73
75
100A – 3 pole
3 (26.7)
240V/50Hz/3ph
L1, L2, L3 and ground
79
78
100A – 3 pole
3 (26.7)
240V/60Hz/3ph
L1, L2, L3 and ground
79
78
100A – 3 pole
3 (26.7)
380V/50 or 60Hz/3ph L1, L2, L3 and ground
47
48
60A – 3 pole
6 (13.3)
400-415V/50Hz/3ph
L1, L2, L3 and ground
43
44
60A – 3 pole
6 (13.3)
440V/60Hz/3ph
L1, L2, L3 and ground
41
41
51A – 3 pole
6 (13.3)
480V/60Hz/3ph
L1, L2, L3 and ground
38
38
50A – 3 pole
6 (13.3)
Table 10