Electrical Requirements
45
M414905
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
50 Pound Gas and Steam Models
Refer to Table 7.
NOTE: Wire sizes were obtained from the 
Canadian Electrical Code for 75 C. wire and are 
intended for use as a guideline only. Electrical 
connections should be made by a qualified 
electrical contractor in accordance with all 
applicable local and national requirements.
NOTE: Electrical specifications below are subject 
to change without notice. Always refer to product 
serial plate for most current specifications of 
product being installed.
NOTE: Use copper conductors only.
NOTE: 3 Phase Only – Each tumbler must be 
connected to its own individual branch circuit 
breaker, not fuses, to avoid the possibility of “single 
phasing” and causing premature failure of the 
motor(s).
7
Serial Plate Rating
Terminal Block 
Connections 
Required
Serial Plate Amps
Recommended Circuit
Nonreversing
Reversing
Breaker Rating
Wire Size
AWG (mm
2
)
120V/60Hz/1ph
L1, Neutral and ground
9.3
N/A
15A – 1 pole
14 (2.08)
200-208V/60Hz/1ph
L1, Neutral and ground
5.1
N/A
10A – 1 pole
14 (2.08)
200-208-240V/60Hz/
1ph
L1, L2 and ground
5.1
N/A
10A – 2 pole
14 (2.08)
230-240V/50Hz/1ph
L1, Neutral and ground
6.3
6.9
15A – 1 pole
14 (2.08)
200-208V/60Hz/3ph
L1, L2, L3 and ground
2.8
4.0
10A – 3 pole
14 (2.08)
200V/50Hz/3ph
L1, L2, L3 and ground
3.3
4.2
10A – 3 pole
14 (2.08)
240V/60Hz/3ph
L1, L2, L3 and ground
2.8
4.0
10A – 3 pole
14 (2.08)
230-240V/50Hz/3ph
L1, L2, L3 and ground
3.1
4.3
10A – 3 pole
14 (2.08)
380V/50 or 60Hz/3ph
L1, L2, L3 and ground
1.6
2.0
10A – 3 pole
14 (2.08)
400-415V/50Hz/3ph
L1, L2, L3 and ground
1.6
2.0
10A – 3 pole
14 (2.08)
440V/60Hz/3ph
L1, L2, L3 and ground
1.4
1.9
10A – 3 pole
14 (2.08)
460-480V/60Hz/3ph
L1, L2, L3 and ground
1.4
1.9
10A – 3 pole
14 (2.08)
N/A = Not Applicable
Table 7