Gas Requirements
IMPORTANT: Any product revisions or conversions 
must be made by the Manufacturer’s Authorized 
Dealers, Distributors or local service personnel.
IMPORTANT: The installation must comply with 
local codes or, in the absence of local codes:
with the latest edition of the “National Fuel 
Gas Code,” ANSI Z223.1/NFPA 54 in the 
U.S.A.,
with CSA-B149.1 Natural Gas and Propane 
Installation Code in Canada,
and Australian Gas Association/Australian 
L.P. Gas Association requirements in 
Australia.
Obtain specific gas service pipe size from the gas 
supplier. Refer to Table 7 for general pipe size.
A dirt and water vapor pipe trap must be furnished and 
installed by customer. Refer to Figure 13
Install a 1 inch (25.4 mm) pipe gas loop to maintain 
equal pressure at all gas connections. Refer to 
Figure 14
NATURAL GAS service must be supplied at 7.0 ± 
1.5 inch water column pressure (1.74 ± 0.37 kPa).
L.P. (Liquefied Petroleum) GAS service must be 
supplied at 11 ± 0.3 inch water column pressure 
(2.74 ± 0.07 kPa).
EUROPEAN GASES – The above data for Natural 
and L.P. Gas does not apply in the EU. Refer to 
Installing Gas Drying Tumblers in the European 
Union
 Section. 
Figure 13 
WARNING
To reduce the risk of fire or explosion, DO 
NOT CONNECT THE GAS LINE TO THE 
TUMBLER IF THE GAS SERVICE IS NOT 
THE SAME AS THAT SPECIFIED ON THE 
TUMBLER SERIAL PLATE! It will first be 
necessary to convert the gas burner 
orifice and gas valve. Appropriate 
conversion kits are available.
W060
WARNING
The tumbler and its individual shut-off 
valve must be disconnected from the gas 
supply piping system during any 
pressure testing of that system at test 
pressures in excess of 1/2 psig (3.45 kPa).
The tumbler must be isolated from the 
gas supply piping system by closing its 
individual manual shut-off valve during 
any pressure testing of the gas supply 
piping system at test pressure equal to or 
less than 1/2 psig (3.45 kPa).
W061
T135I
1
Gas Line to Tumbler Controls
2
Shut-Off Valve
3
Gas Supply Piping System
4
Gas “T” Fitting
5
6 in. (152 mm) Minimum Gas Pipe
6
Gas Pipe Cap
7
Dirt and Water Vapor Trap
8
1/8 in. (3.2 mm) NPT plugged tapping 
accessible for pressure testing. Gauge 
connection located upstream from tumbler 
gas supply connection.
WARNING
To reduce the risk of fire or explosion, if 
the tumbler is to be connected to 
Liquefied Petroleum (L.P.) gas, a vent to 
the outdoors must be provided in the 
room where the tumbler is installed.
W062
T378I
1
2
3
4
5
6
7
8