Electrical Requirements
47
70269701
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Connecting Electrical Service 
The following steps outline the procedure for 
connecting electrical service to the tumbler. 
3 Phase Models – Each tumbler must be 
connected to its own individual branch circuit 
breaker, not fuses, to avoid the possibility of 
“single phasing” and causing premature 
failure of the motor(s).
Electrical service must be connected using the 
appropriate permanent rigid metal conduit 
system.
Service conductors must be copper only.
For an existing service, determine your service voltage 
and conductor amperage. Carefully review the tumbler 
serial plate ratings and Electrical Requirements 
section of this manual. If service is inadequate it must 
be upgraded by a qualified electrical contractor. Never 
connect an improper or inadequate service to any 
machine.
Configuring Your Tumbler for Other 
Service Voltages
Several gas and steam tumbler models have been 
designed to be field convertible to other service 
voltages. Refer to Table 8 for these models:
NOTE: Electric models are not field convertible 
and must be connected to service specified on serial 
plate.
If tumbler requires conversion for use on another 
service voltage, complete the steps detailed in the 
Conversion Instructions section prior to connecting 
service to machine
.
If tumbler does not require conversion or has been 
converted according to the Conversion Instructions 
section of this manual, continue with step 1.
NOTE: The wiring diagram is located inside the 
junction or contactor box. 
1. For new service, install a circuit breaker or fused 
disconnect of proper voltage and current rating as 
close to each tumbler as possible.
2. Route service conduit from service breaker panel 
or disconnect panel to tumbler service connection 
box. Conduit routing should not obstruct access 
for maintenance or servicing. Refer to Service/
Ground Location
.
3. Pull conductors through conduit and attach to 
circuit breaker and ground connection. Secure 
service ground wire to the grounding screw or 
lug. Attach service conductors to appropriately 
labeled positions on the terminal block. Make 
sure all connections are secure.
4. Complete ferrite installation instructions for all 
gas and steam OPL Micro models.
5. Check electrical service phase sequence (3 Phase 
models only) as follows:
a. Energize the electrical service and 
momentarily start the tumbler. Check the 
direction of cylinder rotation. If the cylinder 
rotates clockwise as viewed from the front, 
the phase sequence is correct. If the cylinder 
rotates counterclockwise, proceed with step b.
b. Disconnect power to machine, disconnect and 
reverse the L1 and L2 connections on the 
terminal block.
If your Serial Plate 
voltage is:
Your tumbler can be 
converted to the 
following voltages:
120 Volt/60 Hertz/
1 Phase
208-240 Volt/60 Hertz/
1 Phase
200-220 Volt/60 Hertz/
1 Phase 
100 Volt/60 Hertz/
1 Phase
200 Volt/50 Hertz/
1 Phase
100 Volt/50 Hertz/
l Phase
240 Volt/60 Hertz/
3 Phase
200-208 Volt/60 Hertz/
3 Phase
380 Volt/50 Hertz/
3 Phase
400-415 Volt/50 Hertz/
3 Phase
Table 8