Electrical Requirements
49
70269701
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Conversion Instructions
If serial plate voltage is:
Tumbler can be converted to the following voltages:
120 Volt/60 Hertz/
1 Phase
2W&G
208-240 Volt/60 Hertz/1 Phase Models:
3W&G
1. Prior to connecting service, locate the black/red wire which runs between 
terminal block and the motor relay or contactor. Refer to figure below.
2. Disconnect the black/red lead from L1 of the terminal block and connect to 
L2 of the terminal block. For stacked tumbler complete steps 1 and 2 for 
upper and lower junction box areas.
3. Sign and date conversion sticker located on back of tumbler.
4. Follow the instructions covered in Connecting Electrical Service section.
240 Volt/60 Hertz/
3 Phase
3W&G
200-208 Volt/60 Hertz/3 Phase Models:
3W&G
1. Prior to connecting electric service, locate transformer configuration jumper 
in junction box area.
2. Remove the 240 Volt jumper and replace it with the 208 Volt jumper located 
in the literature packet in cylinder.
3. For stacked tumblers, repeat steps 1 and 2 for each upper and lower unit.
4. Sign and date conversion sticker located on back of tumbler.
5. Follow the instructions covered in Connecting Electrical Service section.