Electrical Requirements
70269701
52
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Electrical Requirements for Gas and 
Steam Models
NOTE: Minimum wire sizes are obtained from 
Canadian Electrical Code Table 2 for 75°C 
Conductors and are intended for use as a guideline 
only. Electrical connections should be made only by 
a qualified electrical contractor in accordance with 
all applicable local and national requirements.
NOTE: Electrical specifications below are subject 
to change without notice. Always refer to product 
serial plate for most current specifications of 
product being installed.
NOTE: Use copper conductors only.
NOTE: Connect to individual branch circuit.
NOTE: 3 Phase Only – Each tumbler must be 
connected to its own individual branch circuit 
breaker, not fuses, to avoid the possibility of “single 
phasing” and causing premature failure of the 
motor(s).
For 25, 30 and 35 Pound Gas and Steam Models:
Table 9 
Serial Plate 
Voltage
Terminal Block
Connections 
Required
Current 
(Amps)
Recommended 
Fuse or
Breaker Rating
(Amps)
Breaker 
Poles
Recommended 
Minimum
Conductor Size
[AWG (mm
2
)]
120V/60Hz/1ph
L1, Neutral, 
and ground
12.0
15
1
14 (2.08)
208-240V/60Hz/
1ph
L1, L2, Neutral, 
and ground
6.7
10
2
14 (2.08)
120V/60Hz/1ph
L1, Neutral, 
and ground
7.5**
10
1
14 (2.08)
208-240V/60Hz/
1ph
L1, L2, Neutral, 
and ground
4.5**
10
2
14 (2.08)
100V/60Hz/1ph
L1, Neutral, 
and ground
11.0
15
1
14 (2.08)
200-220V/60Hz/
1ph
L1, Neutral, 
and ground
5.8
10
1
14 (2.08)
100V/50Hz/1ph
L1, Neutral, 
and ground
12.1
20
1
12 (3.31)
200V/50Hz/1ph
L1, Neutral, 
and ground
7.5
10
1
14 (2.08)
230-240V/50Hz/
1ph
L1, Neutral, 
and ground
7.5
10
1
14 (2.08)
200-208V/60Hz/
3ph
L1, L2, L3,
and ground
3.2
10*
3
14 (2.08)
240V/60Hz/3ph
L1, L2, L3, 
and ground
3.2
10*
3
14 (2.08)
200V/50Hz/3ph
L1, L2, L3, 
and ground
2.9
10*
3
14 (2.08)
230-240V/50Hz/
3ph
L1, L2, L3, 
and ground
3.5
10*
3
14 (2.08)
380V/50Hz/3ph
L1, L2, L3, 
and ground
1.5
10*
3
14 (2.08)
400-415V/50Hz/
3ph
L1, L2, L3, 
and ground
1.6
10*
3
14 (2.08)
460-480V/60Hz/
3ph
L1, L2, L3, 
and ground
1.6
10*
3
14 (2.08)
*
3 Phase machines should not have fuses, breakers only.
**
Special low Amp blower model, 25 Pound only