Read Status Options
4. Read Status
Unimode 400 Operations PN 50709:A  10/20/97
21
System Parameters
To read System Parameters, follow these steps.
1.
Select Read Point from the Read Status screen to display the Read Point screen 
(Figure 11):
2.
Press <Z>, <S0>, <Enter> to display the System Parameters screen, which 
typically displays as shown in Figure 22:
Figure 22  System Parameters Screen 0
Table 15 contains descriptions of the items shown on System Parameter Screen (Figure 
22):
Table 15  System Parameters
Parameter
Description
Set to...
SIL INH=060
Silence Inhibit timer in 
seconds. Required in 
Canada and some areas of 
the USA.
0 – no timer; or the timer duration 
in seconds. 
AUTO=600
Automatic Silence timer in 
seconds.
0 – no timer; or the timer duration 
in seconds. 
VERIFY=30 
Alarm Verification timer
0 – no timer; or the timer duration 
in seconds. 
USA TIME
Time/date display format 
USA TIME or EUR TIME 
TERM_SUPERV=YES 
Terminal supervision 
YES – To supervise the wiring of 
a terminal mode ADT-LCD-80. 
NO – No Terminal mode and no 
ADT-LCD-80 supervision.
LocT 
One of three operating 
modes of a PC or terminal 
connected to the control 
panel (through TB2 PC/
Terminal). For a complete 
list of functions, refer to the 
Unimode 400 Installation 
Manual. 
LocT – terminal connected to 
control panel and located in the 
same room as the control panel.
LocM – terminal connected to 
control panel but requires 
password for operation.
RemT – terminal connected 
through a modem for Read Status 
operations only.
BLINK=Y
Blink LEDs on intelligent 
devices during polling (for 
certain applications).
Y – blink LED;  or
N – do not blink LED.
ST=4
NFPA wiring style operation 
for the SLC loop
4 – Style 4 SLC loop; or
6 – both Style 6 and Style 7 SLC 
loop.
ACS=N
Use ACS Selection Groups 
(refer to the Unimode 400 
Installation Manual for 
details).
N – No annunciator selected; or
Y – Select and display ACS 
Selection Groups.
SIL INH=060 AUTO=600 VERIFY=30 USA TIME
TERM SUPERV=NO LocT BLINK=Y ST=4 ACS=N