ADT Security Services 400 Manuel D’Utilisation
Read Status Options
4. Read Status
Unimode 400 Operations PN 50709:A 10/20/97
21
System Parameters
To read System Parameters, follow these steps.
1.
Select Read Point from the Read Status screen to display the Read Point screen
(Figure 11):
(Figure 11):
2.
Press <Z>, <S0>, <Enter> to display the System Parameters screen, which
typically displays as shown in Figure 22:
typically displays as shown in Figure 22:
Figure 22 System Parameters Screen 0
Table 15 contains descriptions of the items shown on System Parameter Screen (Figure
22):
22):
Table 15 System Parameters
Parameter
Description
Set to...
SIL INH=060
Silence Inhibit timer in
seconds. Required in
Canada and some areas of
the USA.
seconds. Required in
Canada and some areas of
the USA.
0 – no timer; or the timer duration
in seconds.
in seconds.
AUTO=600
Automatic Silence timer in
seconds.
seconds.
0 – no timer; or the timer duration
in seconds.
in seconds.
VERIFY=30
Alarm Verification timer
0 – no timer; or the timer duration
in seconds.
in seconds.
USA TIME
Time/date display format
USA TIME or EUR TIME
TERM_SUPERV=YES
Terminal supervision
YES – To supervise the wiring of
a terminal mode ADT-LCD-80.
NO – No Terminal mode and no
ADT-LCD-80 supervision.
a terminal mode ADT-LCD-80.
NO – No Terminal mode and no
ADT-LCD-80 supervision.
LocT
One of three operating
modes of a PC or terminal
connected to the control
panel (through TB2 PC/
Terminal). For a complete
list of functions, refer to the
Unimode 400 Installation
Manual.
modes of a PC or terminal
connected to the control
panel (through TB2 PC/
Terminal). For a complete
list of functions, refer to the
Unimode 400 Installation
Manual.
LocT – terminal connected to
control panel and located in the
same room as the control panel.
LocM – terminal connected to
control panel but requires
password for operation.
RemT – terminal connected
through a modem for Read Status
operations only.
control panel and located in the
same room as the control panel.
LocM – terminal connected to
control panel but requires
password for operation.
RemT – terminal connected
through a modem for Read Status
operations only.
BLINK=Y
Blink LEDs on intelligent
devices during polling (for
certain applications).
devices during polling (for
certain applications).
Y – blink LED; or
N – do not blink LED.
N – do not blink LED.
ST=4
NFPA wiring style operation
for the SLC loop
for the SLC loop
4 – Style 4 SLC loop; or
6 – both Style 6 and Style 7 SLC
loop.
6 – both Style 6 and Style 7 SLC
loop.
ACS=N
Use ACS Selection Groups
(refer to the Unimode 400
Installation Manual for
details).
(refer to the Unimode 400
Installation Manual for
details).
N – No annunciator selected; or
Y – Select and display ACS
Selection Groups.
Y – Select and display ACS
Selection Groups.
SIL INH=060 AUTO=600 VERIFY=30 USA TIME
TERM SUPERV=NO LocT BLINK=Y ST=4 ACS=N
TERM SUPERV=NO LocT BLINK=Y ST=4 ACS=N