SPX Cooling Technologies Marley MH Fluid Cooler User Manual

Page of 36
27
additional cleaning. Refer to “Fluid Cooler Cleaning” section—page 21. 
Consult your water treatment expert as to prudent biological evaluation 
testing.
Geareducer models used on MH Fluid Coolers are designed for 5-year 
oil change intervals. To maintain five-year change intervals, use only 
oil designed specifically for these Geareducers. If, after five years, 
turbine-type mineral oil is used, the oil must be changed semiannu-
ally. Refer to the Geareducer User Manual for oil recommendations 
and further instructions.
annually: Relubricate motor(s) according to the manufacturer’s instruc-
tions. See instructions on the next page for towers with the motor located 
outside the plenum option.
Check to see that all bolts are tight in the fan and mechanical equipment 
region, including the fan cylinder and fan guard. Refer to Component User 
Manuals for torque values. 
Inspect the fluid cooler thoroughly, making maximum use of instructions 
given in the separate user manuals. Check structural bolted connections 
and tighten as required. Make preventive maintenance repairs as neces-
sary.
Check to see that all bolts are tight in the fan and mechanical equipment 
region, including the fan cylinder and fan guard. Refer to Component User 
Manuals for torque values.
Every 5 Years: If equipped, change Geareducer oil. Refer to the Geareducer 
User Manual
 for instructions.
Motor relubrication instructions
Motor located outside plenum option. Double-flow models MHF706 and 
MHF707 only.
Open and lock out disconnect switch to make certain motor cannot 
be started.
1.   Remove guard as shown in 
Figure 4. Opposite end motor bearing is 
accessible from outside the tower.
2.   Remove grease fill and relief plugs at both shaft extension end and op-
posite end bearings and remove hardened grease, using clean wire.
Maintenance
Note