.   Insert grease fittings in grease fill openings and add grease until grease 
is forced out through relief openings.
4.   Replace fill plugs and operate mechanical equipment 0 minutes to 
one hour to purge excess grease at grease relief opening.
5.   Reinstall grease relief plugs and reinstall guard.
6.   Resume normal fluid cooler operation.
Seasonal Shutdown instructions
When the system is to be shut down for an extended period of time, it is 
recommended that the recirculation water system be drained. Leave the 
basin drains open. 
Draining  the  coil  is  not  recommended—draining  promotes  corro-
sion inside the coil tubes. See protecting coil in Freezing weather 
on page 18. 
During shutdown, clean the fluid cooler (see Warning, page 21) and make 
any necessary repairs. Eliminators and louvers are easily removed to gain 
access to the coil. Pay particular attention to mechanical equipment sup-
ports and sheaves or coupling (or drive shafts).
Following each year’s shutdown and cleaning, inspect the fluid cooler’s 
metal surfaces for evidence of the need to apply a protective coating. Do 
not misinterpret grime as a need to have the tower painted. If relatively 
bright metal can be exposed by cleaning, consider that the galvanizing 
 
Motor
Guard
Steel Side Casing
Attachment Screw
Grease Relief Plug
Grease Fill Plug
Figure 4
Maintenance
 Caution