UNIT LOCATION
The YCUL Condensing Units are designed for outdoor 
installation.  When  selecting  a  site  for  installation,  be 
guided by the following conditions:
1.For outdoor locations of the unit, select a place having 
an adequate supply of fresh air for the condenser.
2. Avoid locations beneath windows or between struc-
tures where normal operating sounds may be objec-
tionable.
3. Installation sites may be either on a roof, or at ground 
level. (See FOUNDATION.)
4. The condenser fans are the propeller-type, and are 
not recommended for use with duct work in the con-
denser air stream.
5. When it is desirable to surround the unit(s), it is rec-
ommended that the screening be able to pass the 
required chiller CFM without exceeding 0.1" of water 
external static pressure.
6. Protection against corrosive environments is available 
by supplying the units with either copper fin, cured 
phenolic, or epoxy coating on the condenser coils. 
The phenolic or epoxy coils should be offered with 
any units being installed at the seashore or where 
salt spray may hit the unit.
In installations where winter operation is intended and 
snow  accumulations  are  expected,  additional  height 
must  be  provided  to  ensure  normal  condenser  air 
flow.
Recommended clearances for units are given in DIMEN-
SIONS. When the available space is less, the unit(s) 
must be equipped with the discharge pressure trans-
ducer option to permit high pressure unloading in the 
event that air recirculation were to occur.
FOUNDATION
The unit should be mounted on a flat and level founda-
tion, ground or roof, capable of supporting the entire 
operating weight of the equipment. Operating weights 
are given in the PHYSICAL DATA tables.
ROOF LOCATIONS – Choose a spot with adequate 
structural strength to safely support the entire weight 
of the unit and service personnel. Care must be taken 
not to damage the roof during installation. If the roof is 
“bonded”,  consult  the  building  contractor  or  architect 
for special installation requirements. Roof installations 
should incorporate the use of spring-type isolators to 
minimize the transmission of vibration into the building 
structure.
Application Data
GROUND LEVEL INSTALLATIONS – It is important 
that the units be installed on a substantial base that will 
not settle, causing strain on the refrigerant lines and 
resulting in possible leaks. A one-piece concrete slab 
with footers extending below the frost line is highly rec-
ommended. Additionally, the slab should not be tied to 
the main building foundation as noises will telegraph.
Mounting holes (11/16" diameter) are provided in the 
steel channel for bolting the unit to its foundation. See 
DIMENSIONS.
For  ground  level  installations,  precautions  should  be 
taken to protect the unit from tampering by or injury to 
unauthorized persons. Screws on access panels will pre-
vent casual tampering; however, further safety precau-
tions, such as unit enclosure options, a fenced-in enclo-
sure, or locking devices on the panels may be advisable. 
Check local authorities for safety regulations.
REFRIGERANT PIPING
When sizing refrigerant pipe for split system air condi-
tioning, consideration must be given to the: (1) Suction 
line pressure drop due to friction, (2) Liquid line pres-
sure drop due to friction, (3) Suction line velocity for oil 
return, and (4) Liquid line pressure drop due to vertical 
rise. Refer to DESIGN PARAMETERS for friction losses 
for both the suction and liquid lines for the condensing 
unit.
On a system where the evaporator blower is located 
below  the  condensing  unit,  the  suction  line  must  be 
sized for both pressure drop and oil return.
When the condensing unit is located below the evapora-
tor blower, the liquid line must be designed for pressure 
drop due to friction loss and vertical rise. If the pressure 
drop due to vertical rise and friction loss exceeds 30 psi, 
some refrigerant will flash before it reaches the thermal 
expansion valve.
All horizontal suction lines should be pitched at least 1/4 
inch per foot in the direction of the refrigerant flow to aid 
the return of oil to the compressor. All suction lines with 
a vertical rise exceeding 3 feet should have a ‘P’ trap 
at the bottom and the top to facilitate oil return. Suction 
lines with a vertical rise exceeding 25 feet should be 
trapped  every  15  feet  to  provide  drain  points  for  the 
oil when the circuit is deactivated. When the circuit is 
reactivated, oil will return to the compressor more quickly 
and in smaller slugs.
For more details, refer to ASHRAE Refrigeration Hand-
book, System Practices for Halocarbon Refrigerants.