2.03  REFRIGERANT CIRCUIT
One (YCUL0016-0040) or two (YCUL0046-0130) inde-
pendent refrigerant circuits will be furnished on each 
unit. All unit piping will be copper, with brazed joints. The 
liquid line will include a field connection shutoff valve with 
charging port located on each condenser circuit. Suc-
tion line connections are provided on each refrigeration 
circuit. Filter drier and sight glass are shipped loose for 
field installation on each refrigerant circuit. 
All expansion valves and liquid line solenoid valves and 
refrigerant field piping are supplied by others.
2.04  HEAT EXCHANGERS
A.   Air Cooled Condenser:
1.    Coils:  Internally  enhanced,  seamless  copper 
tubes, mechanically expanded into aluminum 
alloy fins with full height collars. Subcooling coil 
an integral part of condenser. Design working 
pressure shall be 450 psig (31 bar).
2.    Fans:  Shall  be  dynamically  and  statically 
balanced, direct drive, corrosion resistant glass 
fiber reinforced composite blades molded into 
low  noise,  full  airfoil  cross  section,  providing 
vertical  air  discharge  from  extended  orifices 
for efficiency and low sound. Each fan in its own 
compartment to prevent cross flow during fan 
cycling. Guards of heavy gauge, PVC (polyvinyl 
chloride) coated or galvanized steel.
3.    Fan  Motors:  High  efficiency,  direct  drive,  6 
pole,  3  phase,  insulation  class  “F”,  current 
protected, Totally  Enclosed Air-Over  (TEAO), 
rigid mounted, with double sealed, permanently 
lubricated, ball bearings.
2.05  CONTROLS
A.   General: Automatic  start,  stop,  operating,  and 
protection sequences across the range of scheduled 
conditions and transients.
B.   Microprocessor  Enclosure:  Rain  and  dust  tight 
NEMA 3R/12 (IP55) powder painted steel cabinet 
with hinged, latched, and gasket sealed door.
C.  Microprocessor Control Center:
1.    Condensing  Unit  control  can  be  set  for  Dis-
charge Air Temperature Control or for Suction 
Pressure  Control.  (Note:  Suction  Pressure 
Control  requires  optional  Suction  Pressure 
Transducers on Models YCUL0016-0066.)
2.    Automatic  control  of  compressor  start/stop, 
anti-coincidence  and  anti-recycle  timers, 
automatic  pump-down  shut-down,  condenser 
fans, unit alarm contacts, and condensing unit 
operation from 0°F to 125°F (-18°C to 52°C) 
ambient. Automatic  reset  to  normal  chiller 
operation after power failure.
3.    Discharge  air  temperature  reset  via  a  Pulse 
Width Modulated (PWM) input signal or up to 
two steps of demand (load) limiting.
4.    Software  stored  in  non-volatile  memory,  with 
programmed  set-points  retained  in  lithium 
battery backed real time clock (RTC) memory 
for minimum 5 years.
5.    Forty character liquid crystal display, descrip-
tions in English (or Spanish, French, Italian, or 
German), numeric data in English (or Metric) 
units.  Sealed  keypad  with  sections  for  Set-
points,  Display/Print,  Entry,  Unit  Options  & 
clock, and On/Off Switch.
6.    Programmable Set-points (within Manufacturer 
limits):  display  language;  suction  pressure 
setting  and  control  range,  remote  reset  tem-
perature  range,  set  daily  schedule/holiday 
for  start/stop,  manual  override  for  servicing, 
low  and  high  ambient  cutouts,  number  of 
compressors,  low  suction  pressure  cutout, 
high  discharge  pressure  cutout,  anti-recycle 
timer (compressor start cycle time), and anti-
coincident timer (delay compressor starts).
7.    Display Data: Suction temperatures (optional), 
low  ambient  temperature  cutout  setting, 
outdoor air temperature, English or metric data, 
suction pressure cutout setting, each system 
suction pressure (optional on YCUL0016-0066 
models),  discharge  pressure  (optional),  dis-
charge  air  reset  via  a  YORK  ISN  DDC  or 
Building Automation  System  (by  others)  via 
PWM input as standard or a 4-20milliamp or 
0-10 VDC input or contact closure with optional 
BAS  interface,  anti-recycle  timer  status  for 
each compressor, anti-coincident system start 
timer  condition,  compressor  run  status,  no 
cooling  load  condition,  day,  date  and  time, 
daily start/stop times, holiday status, automatic 
or  manual  system  lead/lag  control  (when 
controlling based on Discharge Air Temperature 
only),  automatic  lead/lag  of  compressors 
within  a  system,  compressor  starts/operating 
hours  (each),  status  of  hot  gas  valves,  and 
fan operation, run permissive status, number 
of compressors running, liquid solenoid valve 
status, load & unload timer status.
8.    System Safeties: Shall cause individual com-
pressor  systems  to  perform  auto  shut  down; 
manual reset required after the third trip in 90 
minutes.  Includes:  high  discharge  pressure, 
Guide Specifications