UltraViolet Devices Air Disinfection User Manual

Page of 12
5
INSTALLATION
L
OCATION
The 
Hygeaire
®
fixture is recommended for use in rooms with good ventilation, with a ceiling height of 9 feet or 
more and where occupants remain for prolonged periods.
Access to the room does not need to be controlled while the fixture is operating.
The louver panels of the 
Hygeaire
®
fixtures protect room occupants from ultraviolet exposure, by directing 
ultraviolet radiation into the upper areas of the room.
Any plans for the installation of the 
Hygeaire
®
fixtures, should take into account the reflectance of the ceiling. 
Some finishes may have reflectances that are objectionably high, making exposure of more than a few hours 
unsafe. If any help is needed in determining the reflectance of a surface, please contact the Factory.
Ultraviolet energy, produced by the germicidal lamp(s), can fade some colors and/or alter the surface of some 
materials especially those directly irradiated by the lamp(s). If any help is needed in determining the ultraviolet 
resistance of any material, please contact the Factory.
The 
Hygeaire
®
LIND 24-EVO fixture is designed to mount horizontally on a vertical surface, or wall, 
approximately 6 ½ to 7 feet above the floor. 
The 
Hygeaire
®
LIND 24-EVO-2PM fixture includes pendant hardware to suspend fixture from the ceiling. 
Standard stem pipe length is 18 inches. Other lengths are available, contact the Factory with requirements.
IINSPECTION
Remove the 
Hygeaire
®
fixture from its shipping carton. Inspect the fixture, and wire leads for damage. Do not oper-
ate if there is any damage to the fixture, and/or wire leads. Lamp(s) are packed separately, to ensure maximum protec-
tion to the lamp(s). Keep the lamp(s) aside until ready for installation. When installing lamp(s) into the fixture, exercise
care not to touch the lamp's glass. Oils deposited, from fingers, on the glass could effect ultraviolet transmission.
The 
Hygeaire
®
Model LIND 24-EVO fixture includes:
1 - Model LIND 24-EVO single lamp fixture with 6 inch lead wires
1 - Germicidal Ultraviolet Lamp
1 - Operating Instructions
The 
Hygeaire
®
Model LIND 24-EVO-2PM fixture includes:
1 - Model LIND 24-EVO-2PM dual lamp fixture with 4 ½ foot lead wires
1 - Pendant Mounting Kit, consisting of:
1 - #19 Crossbar
1 - #11 Canopy
2 - 3/8" IP Stems 18 inches long
2 - #14 3/8" IP Slip Rings
6 - #22 3/8" IP Locknuts
2 - Germicidal Ultraviolet Lamps
1 - Operating Instructions