Emerson Process Management 3422 User Manual

Page of 398
 Reference, Installation, and Operations Manual
Section 5: Startup and meter configuration
3-9000-743 Rev S
June 2013
Communications setup
 101
Ports A, B, and C support ASCII and RTU Modbus protocols (as detailed in 
) which are 
automatically detected on a per-port basis. 
Modbus addresses are software configurable (from 1 to 247) on a per-port basis. Ports A and B 
operate only as Modbus slaves. Port C can operate as either a Modbus slave (for general 
communication) or a Modbus master.
Baud rates are software selectable on a per-port basis from the following:
ASCII Modbus: 1200, 2400, 9600, 19200, 38400, 57600, 115000 bps
RTU Modbus: 1200, 2400, 9600, 19200, 38400 bps
When Belden wire No. 9940 or equivalent is used, the maximum cable length for RS-232 
communications at 9600 bps is 88.3 meters (250 ft.) and the maximum cable length for RS-485 
communication at 57600 bps is 600 meters (1970 ft.).
Port B supports a special override mode which forces the port to use known communication 
values (19200 baud, address 32) (
). (Note that the protocol is still auto-
detected.) This mode is expected to be used during meter commissioning (to establish initial 
communication) and in the event that the user cannot communicate with the meter (possibly 
due to an inadvertent communication configuration change).
The Ethernet port IP address, subnet mask, and gateway address are software-configurable. In 
addition, a meter can be configured to act as a DHCP (Dynamic Host Configuration Protocol) 
server. The DHCP server facility is not intended to act as a general purpose DHCP server for a 
wider network. To this end, no user control is provided over the class or range of IP addresses the 
unit provides. A standard twisted pair (Cat-5) cable should be used for Ethernet wiring.
Table 5-2  Supported Modbus Protocols
Modbus 
Protocol
Number of Start 
Bits
Number of Data 
Bits
Parity Type
Number of Stop 
Bits
ASCII
1
7
odd or even
1
RTU
1
8
none
1