Emerson Process Management 3422 User Manual

Page of 398
 302
Modbus Communication
Upgrading a Mark II to a Mark III
 Reference, Installation, and Operations Manual
June 2013
3-9000-743 Rev S
C.3
Modbus Communication
C.3.1
Protocols
The Mark III meter supports ASCII and RTU Modbus communication. For ASCII Modbus, both 
7E1 and 7O1 are supported. For RTU Modbus, 8N1 is supported. The communication ports 
provide automatic protocol detection - only the baud rate and Modbus ID need to be specified. 
Refer to 
 for details on configuring the meter communication parameters.
C.3.2
Registers
The Mark III uses a database for managing its information in which each piece of information is 
stored in a database point. The meter utilizes a mapping file for cross-referencing database 
points with Modbus registers for Modbus data access. Refer to 
 for further details.
The Mark III maintains backward compatibility to Mark II Modbus registers whenever possible. 
The 
UnitsSystem register selects the units for Modbus communications. Available options are 
U.S. Customary and Metric. These are the units in which the software Field Setup Wizard 
displays properties. These are also the units with which the meter reports all of its rates and 
volumes using Modbus communications. The selected units system applies only to registers 
above 10000 and in the 2000-8999 range, other registers below 10000 are read in metric units 
only to maintain Mark II compatibility. US customary units is the default setting.
For Modbus access information for a particular data point, consult 
Daniel MeterLink online help. (There is a help topic for each data point. From Daniel MeterLink, 
click on Help, click on Mark III Registers Reference, select the Index tab, start typing the data 
point name until the desired point is highlighted, and then click the Display button.)
The Modbus map is available in Microsoft Excel format (MARK III Modbus Table.xls) on the Daniel 
MeterLink CD and the Daniel websit
). Note that on the website, the file name may include 
the file size (MARK III Modbus Table 386KB.xls).
The Daniel MeterLink program includes a means of converting a Mark II meter configuration to a 
Mark III meter configuration for use in upgrading electronics heads. This feature is discussed in 
 below.
C.3.3
Log Access
Due to the Mark III meter’s enhanced log retrieval methods, accessing log records via Modbus 
communication is not supported. All log records (daily, hourly, audit, alarm, and system) are 
optionally accessible via Daniel MeterLink (see 
).