ReaR wall VenT applICaTIon
When installed as a rear vent unit this appliance may be 
vented directly to a termination located on the rear wall 
behind the appliance.
  Only MHSC venting components are approved to be 
used in these applications (Refer to ‘Venting Compo-
nents’ listed for different installation requirements).
  The maximum horizontal distance between the rear of 
the appliance (or end of the transition elbow in a cor-
ner application) and the outside face of the rear wall is 
0” (508 mm). Figure 14
  Only one 45° elbow is allowed in these installations.
  Minimum clearances between vent pipe and combus-
tible materials are as follows:
 
Top - 3” (76 mm) 
 
- except at outside wall 1" (5 mm)
 
Sides - 1” (5 mm)
 
Bottom - 1” (5 mm)
FP2292
rear vent top vu
20”
(508 mm)
Max.
Rear Vent Top 
View
Figure 15 - 
Rear Vent Application, No Elbows
ReaR wall VenT InSTallaTIon  - TwIST 
loCK pIpe
Step 1
Locate and cut the vent opening in the wall.
For combustible walls first frame in opening. Figure 16
noTe:  When using flex vent, the opening will have to be 
measured  according  to  the  1”  (5  mm)  rise  in  4”  (610 
mm) vertical run.
Combustible  walls:  Cut  a  9B\,”H  x  9B\,”  W  (44  x  44 
mm) hole through the exterior wall and frame as shown. 
Figure 16
noncombustible  walls:  Hole  opening  should  be  7Z\x” 
(191 mm) diameter.
Step 2
Secure firestop to the inside frame, center in the 9B\," x 
9B\," vent opening.
Step 3
Measure the horizontal length requirement for the venting 
including a ” (51 mm) overlap, i.e. from the elbow to the 
outside wall face plus ” (51 mm). Figure 15
Step 4
Install the 4” (10 mm) vent to the appliance collar and 
secure with 3 sheet metal screws. Install the 7” (178 mm) 
vent pipe to the appliance collar and secure with 3 sheet 
metal screws. It is not necessary to seal this connection. 
If a 45° elbow is being used attach the elbow to the appli-
ance in the same manner then attach the venting to the 
elbow.
It is critical that there is no downward slope 
away  from  the  appliance  when  connecting 
the vent or elbow.
Step 5
Guide the venting through the vent hole as you place the 
appliance in its installed position. Guide the 4”   (10 mm) 
and  7”  (178  mm)  collar  of  the  vent  termination  into  the 
outer ends of the venting. Do not force the termination. If 
the vent pipes do not align with the termination, remove 
and realign the venting at the appliance flue collars. Fig-
ure 17
. Attach the termination to the wall as outlined in the 
instruction sheet supplied with the termination.
VenTInG InSTallaTIon 
VO584-100
Vent Opening
2/99   djt
Vent opening for Combustible walls
9B\,”
(44 mm)
Min.
Fireplace Hearth
Framing Detail
opening for noncombustible wall
7Z\x”
(190 mm)
Fireplace Hearth
FP93
Figure 16 -  
Locate vent opening on wall
9B\,”
(44 mm) Min.