Monessen Hearth CDV7 User Manual

Page of 68
CDVSC7 & CDV7 Series Gas Fireplace
69D3011
1
•  The maximum number of 90° elbows per side wall in-
stallation is three (3). Figure 21
•  If a 90° elbow is fitted directly on top of the fireplace 
flange the maximum horizontal vent run before the ter-
mination or a vertical rise is 36” (914 mm). Figure 22
•  If a 90° elbow is used in the horizontal vent run (level 
height  maintained)  the  horizontal  vent    length  is  re-
duced by 36” (914 mm). Figures 22 & 23. This does 
not  apply  if  the  90°  elbows  are  used  to  increase  or 
redirect a vertical rise. Figure 21
example:  According  to  the  vent  graph  (Page  15)  the 
maximum horizontal vent length in a system with a 7Z\x’ 
(.3 m) rise is 0’ (6 m) and if a 90° elbow is required in 
the horizontal vent it must be reduced to 17’ (5. m).
In Figures 24 & 25, dimension A plus B must not be great-
er than 17’ (5.m)
•  The maximum number of 45° elbows permitted per in-
stallation is six (6). These elbows can be installed in 
either the vertical or horizontal run.
•  For each 45° elbow installed in the horizontal run, the 
length of the horizontal run MUST be reduced by 18” 
(457 mm). This does not apply if the 45° elbows are 
installed on the vertical part of the vent system.
•  The maximum number of elbow degrees in a system is 
70°. Figure 25
Example: 
Elbow 1  =  90°
 
Elbow   =  45°
 
Elbow 3  =  45°
 
Elbow 4  =  90°
 Total angular variation  =  70°
3 x 90° 
Elbows
3 x 90° 
Elbows
FP1176
Figure 21 -
Maximum three (3) 90° elbows per installation
Max 20"
Max 20"
36" 
(914mm) 
Max.
36" 
(914mm) 
Max.
FP1177
Figure 22 -
 Maximum horizontal run with no rise
VenTInG InSTallaTIon     
7’6"
(2.3m)
A
B
A + B = 17’ (Max.)
(5.2m)
FP1178
Figure 23 - 
Horizontal Run Reduction
V584-201
Horizontal Run
2/99   djt
a
10’
(3 m)
7’
(.1 m)
7’6"
(.3 m)
V584-01
B
Figure 24 - 
Maximum Vent Run with Elbows
1
2
3
4
1
2
3
4
1 + 2 + 3 + 4 = 270°
FP1180
Figure 25 - 
Maximum Elbow Usage